智能电力监测仪使用说明书

2019-04-16 16:34

PMAC9900智能电力监测仪

使用说明书

江苏无线电厂有限公司

PMAC9900智能电力监测仪使用说明 目 录

第一章 简介 ............................................................................................................................ 2 第二章 安装 ............................................................................................................................ 3

2.1 安装环境、尺寸及要求 ............................................................................................... 3 2.2 PT和CT的选择 ............................................................................................................ 3 2.3 PT和CT的连接 ............................................................................................................ 3 2.4 接地 ............................................................................................................................... 3 2.5 三相星型(Y)系统连接 ............................................................................................. 3 2.6 三相△形(DELTA)系统的连接 ................................................................................. 8 2.7 通讯连接 ....................................................................................................................... 9 2.8 精度 ............................................................................................................................ 12 2.9 现场安装与维护 ........................................................................................................ 12

第三章 基本操作................................................................................................................ 13

3.1 开机 ............................................................................................................................ 13 3.2 显示模式 .................................................................................................................... 13

3.2.1 概述 ................................................................................................................. 13 3.2.2 “相序”键 ..................................................................................................... 14 3.2.3 相显示 ............................................................................................................. 14 3.2.4 “功能”键 ..................................................................................................... 15 3.2.5 电能参数显示 ................................................................................................. 16 3.3 编程模式 .................................................................................................................... 17

3.3.1 编程步骤 ......................................................................................................... 17 3.3.2 操作参数的描述 ............................................................................................. 18 3.3.3 选择直接输入或PT输入和定置PT电压量程 ............................................. 22 3.3.4 设置电流(AMPS)量程 ..................................................................................... 22 3.3.5 设置电压模式 ................................................................................................. 23 3.3.6 显示格式 ......................................................................................................... 23 3.3.7 调节显示对比度 ............................................................................................. 23 3.3.8 设置通讯参数 ................................................................................................. 23 3.3.9 清除和复位功能 ............................................................................................. 23 3.3.10重新设定密码 ................................................................................................ 23 3.3.11定值越限设置 ................................................................................................ 23

第四章 定值越限................................................................................................................ 24

4.1 概述 ............................................................................................................................ 24 4.2 参数设定 .................................................................................................................... 24 4.3 限值设定注意事项 .................................................................................................... 25

第五章 通讯 ......................................................................................................................... 25 第六章 故障信息................................................................................................................ 26 附录A PMAC9900 机械尺寸和安装尺寸................................................................. 27 附录B PMAC9900技术指标.......................................................................................... 29

PMAC9900标准电力监控仪使用说明

第一章 简介

PMAC9900标准电力监测仪是基于16位单片机的、直接交流采样的三相电量测量仪表。具有功能齐全、经济实用、可靠性高、抗干扰能力强等众多优点,可取代各种变送器和指示仪表、频率计、功率因数表等常规仪表。

PMAC9900采用测量主体和显示模块分开的方式,便于安装,可广泛地应用于工业和商业配电屏和开关装置及各类自动化系统中。

PMAC9900通信功能强大,具有光电隔离的RS-485通讯口,RS-485为两线局域网,每个环路可接32台仪表,通讯速率为300-19200波特。PMAC9900开放的主/从方式的串行通信协议(与MODBUS协议兼容)使其可以与PMAC系列监控仪及其它监控单元一起构成高效经济的电力监控网络。 通过面膜按键或上位微机可将PMAC9900设定为Y、Δ等多种线制而无须进行端子接线的改动,以下为PMAC9900的标准测量值:

相电压 线电压 电 流 总功率 总电度 有功功率 无功功率 视在功率 有功电度 无功电度 视在功率电度 功率因数 频率 注:以上参数除电度外均有最大、最小值

PMAC9900接线简单,直接连接电流互感器而不需变送器,4线Y系统347/600V以下不需电压互感器。

PMAC9900的所有内部参数如电压、电流量程、电压模式(Y、△)、波特率、密码等既可由面板按键设定,也可由计算机通过通讯口远方设定,设置参数及测量数据在断电后十年不丢失,参数设置具有口令保护。

PMAC9900具有两路继电器输出,可以对三相电压或三相电流进行定值设置,实现简单的定值越限监测并报警输出。

Va 、Vb 、Vc、V平均 Vab、Vbc、V ca、V平均 Ia、Ib、 Ic、I平均 KW总 KWH总 KWa、KWb、KWc、KW总 KVARa、KVARb、KVARc、KVAR总 KVAa、KVAb、KVAc、KVA总 KWH输入、KWH输出 KVARH输入、KVARH输出、KVARH总 KVAH总 PFa、PFb、PFc、∑PF F 2

PMAC9900智能电力监测仪使用说明 第二章 安装

2.1 安装环境、尺寸及要求

· 仪表应尽量安装在干燥、通风良好并远离热源和强(电)磁场的地方,PMAC9900 工作温度范围为:-40℃~+55℃。 · 安装尺寸见附录A · 工作电源: 24V±10%

· 电气连接用12-14号导线,RS-485通讯采用22号屏蔽双绞线。

2.2 PT和CT的选择

PT选择:PMAC9900可直接连接100/173V、220/381V、240/415V或277/480V四线和三线Y型系统或347/600V四线Y型系统,也可采用次级为100V的PT输入。如系统电压超过347/600V,则必须用 PT。PT用于将系统L-N(Y形)或L-L(△形)电压降至100V满刻度范围,PT按以下方式选择:

a) 星 形(Y): PT初级额定值=VLN(或最接近较高标准值的值)

PT次级额定值=100V

b) 三角形(△): PT初级额定值=VLL

PT次级额定值=100V

PT质量直接影响系统精度,因而PT必须有良好的线性和相间关系,才能保证电压、有功和功率因数(PF)的读数有效。

CT选择:CT次级额定值由PMAC9900的电流输入选项决定,标准值为5A。

2.3 PT和CT的连接

图2.5.1到2.6.2描述了各种接线方式。输入电流、电压的相序和极性对装置的正确操作是很重要的,引入PT的各相电压,将由断路器或保险丝保护,如果PT的额定功率超过25W,则次级要加保险丝。

注意:在PT初级的激励下,PT次级能产生危险的电压和电流。因此对装置安装和操作时,需采取安全预防措施(如去掉PT保险)。CT应通过短接端子或测试端子连到仪表,以便于CT的安全连接和断开。

注意:当CT次级开路时,在初级激励下,将产生危险的电压和电流,因此在安装和维护时,需采取预防措施(如短接CT次级等)。

2.4 接地

PMAC9900的地必须用大于14号的导线连接到开关装置的地,以使噪音抑制和瞬间保护电路的功能能正常发挥。接地端子(G)作为PMAC9900测量参考点,同时连到仪表外壳,一个连到大地的好的低阻抗地是精确测量的重要保证,不要将金属门作为接地,必须严格按要求接地。

2.5 三相星型(Y)系统连接

图2.5.1到2.5.4为4线和3线Y型系统接线图。PMAC9900检测各相线对地的电压,如果监测