龙源期刊网 http://www.qikan.com.cn
交流并行输电线路电磁环境影响分析方法及减缓措施探讨
作者:姚欢 夏远芬 杨光俊 方燕 来源:《环境与发展》2018年第03期
摘要:受土地资源和城市规划的影响,越来越多的高压交流输电线路采用并行架设,由此导致并行输电线路对电磁环境的叠加影响。根据《环境影响评价技术导则 输变电工程》(HJ24-2014),对330KV及以上并行输电线路的电磁环境影响应采取类比监测或模式预测的方式进行预测。本文以实例对比了上述两种方法预测结果的相关性,并具体分析了两种方法的适用性,在此基础上,还探讨了并行输电线路电磁环境的减缓措施。 关键词:并行输电线路;类比监测;模式预测;减缓措施
中图分类号:X837 文献标识码:A 文章编号:2095-672X(2018)03-0022-02 DOI:10.16647/j.cnki.cn15-1369/X.2018.03.011
Abstract:Affected by land resources and urban planning, more high voltage AC transmission lines are set up in parallel,and this will lead to the superposition of the parallel transmission lines to the electromagnetic environment. According to(HJ24-2014),the influence of the electromagnetic environment on the parallel transmission lines of 330 thousand volts or above should be predicted by analogy or model prediction.In this paper, the correlation between the predicted results of the two methods is compared with two examples,and the applicability of the two methods is analyzed.On this basis, the mitigation measures for the electromagnetic environment of parallel transmission lines are discussed.
Keywords:Parallel transmission lines;Analogical monitoring;Model prediction;Mitigation measures
交流输电线路是输变电工程的一部分,是输送电能的重要基础设施,在为现代社会发挥作用的同时,不可避免产生一定的环境影响,主要的影响因子为电磁环境。在交流输电线路走廊规划时,受城市建设及土地规划的影响,越来越多的输电线路在设计选线阶段即考虑与已有的线路并行走线,由此可能导致对并行线路沿线电磁环境的叠加影响[1-2]。
《环境影响评价技术导则 输变电工程》(HJ24-2014)明确规定要对330kV及其以上电压等级的并行线路电磁环境影响评价因子进行分析,分析的方法可采用模式预测或类比监测。本文以两种不同架设方式的特高压并行输电线路为例,同时采用实际监测和模式预测的方法对其电磁环境影响进行预测,一方面分析两种预测方法的实用性,另一方面探讨并行输电线路的电磁环境减缓措施,以期为同类工程提供参考。