继电保护 任务书(2)

2019-03-15 22:37

XL20*= XL20/ ZB=48/132.25=0.363

(3) 线路L3等值电抗计算

正序以及负序电抗:XL3= X1L3=0.4×90=36Ω

XL3*= XL3/ ZB=36/132.25=0.2722

零序电抗:XL30= X0L3= 3X1L3=3×0.4×90=108Ω

XL30*= XL30/ ZB=108/132.25=0.8166

(4) 线路L4等值电抗计算

正序以及负序电抗:XL4= X1L4=0.4×25=10Ω

XL4*= XL4/ ZB=10/132.25=0.0756

零序电抗:XL40= X0L4= 3X1L4=3×0.4×25=30Ω

XL40*= XL40/ ZB=30/132.25=0.2268

2.2.2变压器等值电抗计算

(1) 变压器T1、T2等值电抗计算

XT1= XT2=(UK%/100)×(VN2×103/ SN)≈40.333Ω XT1*= XT2*=XT1/ ZB=40.333/132.25=0.3050 (2) 变压器T3等值电抗计算

XT3=(UK%/100)×(VN2×103/ SN)≈21.175Ω XT3*=XT3/ ZB=21.175/132.25=0.1601 (3) 变压器T4、T5、T6、T7等值电抗计算

XT4= XT5=XT6= XT7=(UK%/100)×(VN2×103/ SN)≈63.5Ω XT6*= XT7* = XT4*= XT5*=0.4802 (4) 变压器T8等值电抗计算

XT1=(UK%/100)×(VN2×103/ SN)≈84.7Ω XT8*= XT8/ ZB=84.7/132.25=0.6405

2.2.3发电机等值电抗计算

(1)发电机G1、G2电抗标幺值计算

XG1* = XG2*=Xd1SB/ SG1= Xd1SB COSφ/ PG1=0.132×100×0.8/25=0.4224 (2)发电机G3电抗标幺值计算

第 6 页 共 47 页

XG3*=Xd3SB/ SG3= Xd3SB COSφ/ PG3=0.129×100×0.8/50=0.2064

2.2.4最大负荷电流计算

(1) B、C母线最大负荷电流计算 最大负荷电流计算(拆算到110KV)

IfhB ·max = IfhC·max = PfhBmax Vav2 / 1.732 U COSφ

=20×103/1.732×115×0.8≈0.1255KA; (2) D母线最大负荷电流计算 最大负荷电流计算(拆算到110KV) IfhD ·max = PfhDmax Vav2 / 1.732 U COSφ

=12×103/1.732×115×0.8≈0.0753KA

2.2.5 各线路运行方式下流过断路器的最大负荷电流

(1) 保护1的最大运行方式:发电机FI、P2、F3全投入,继开线路L1;通

?131?131?79?341A过保护1的最大负荷电流为I;保护1的最小运行方fh?max式:发电机F3停,线路全部运行。

(2) 保护2的最大运行方式:发电机Fl、P2、F3全投入,断开L3回路;通

?131?131?79?341A过保护2最大负荷电流为I。保护2的最小运行方式;fh?maxF3停,线路全部运行。

(3) 保护4的最大运行方式:Fl、F 2、F3全投,继开线路L3;通过保护4

?131?79?210A的最大负荷电流为I。保护4的最小运行方式:F3停,线fh?max路全部运行。

(4) 保护5的最大运行方式:F1、F2、F3全投入,断开线路L1;通过保护

?131A5的最大负荷电流为Ifh。保护5的最小运行方式:F3停,线路全部运?max行。

(5) 保护7的最大运行方式:F1、F2、F3全投,线路全部运行;通过保护7

?79A的最大负荷电流为Ifh。 ?max(6) 保护3和保护6因正常运行时不可能有正向电流通过,要是有正向电流

通过,一定是线路发生故障。为此,在保护3和保护7上只需判别电流(功率)的方向即可,故不用分析保护3和保护6的运行方式。

第 7 页 共 47 页

3短路电流计算

3.1电网等效电路图

由于短路电流计算是电网继电保护配置设计的基础,因此分别考虑最大运行方

式(三台发电机全部投入,系统环网取开网运行)时各线路未端短路的情况,最小运行方下(三台中最小的一台投入,系统按环网计算)时各线路未端短路的情况。电网等效电路图如图3.1所示

图3.1电网等效电路图

3.2短路电流计算

3.2.1 d1点发生短路时流过断路1

(1) d1点短路最大运行方式下等值图如图3.2.1(a)

3.2.1(a)d1点短路时最大运行方式下的等值电路图

进一步简化后得图3.2.1(b)

3.2.1(b)简化图

XGT=(XG1+XT1)×(XG2+XT2)/(XG1+XT1+XG2+XT2)=0.3637

第 8 页 共 47 页

XGT3=XG3+XT3=0.2064+0.1601=0.3665 XL=XL1+XL2+XL3=0.1512+0.121+0.2722=0.5444

图3.2.1(b) 正序短路电路图

其中:XdT=XGT×XGT3/(XGT+XGT3)=0.3637×0.3665/(0.3637+0.3665)=0.18255 Xff1=XdT+XL=0.18255+0.5444=0.72695

Id1·max*=E/Xff1=1.05/0.72695≈1.4444 Id1·max=Id1·max*IB=1.4444×0.502≈0.725KA (2)最小运行方式两相短路正序短路电流

Xff1=Xd1+XT1+XL=0.4224+0.3050+0.5444=1.2718 Xff1(2)(2)=Xff1

Ifa(1)(2)=Vf(0)/(Xff1+Xff1(2)(2))=Vf(0)/2Xff1=1.05/2×1.2718=0.4128 If(2)*=1.732Ifa(1)(2)=1.732×0.4128=0.7150 If(2)=If(2)*IB=0.7150×0.502=0.3589KA (3)最大运行方式两相短路零序短路电流.

图3.2.1(c)零序短路电路图

XTT(0)=XT1(0) /2=0.1525

XT(0) =0.1525×0.1601/(0.1525+0.0.1601)=0.0781

XTBL(0) =(0.4536+0.0781)×0.2401/(0.4536+0.0781+0.2401)=0.167 XTL(0) =(0.2268+0.6405)×0.2401/(0.2268+0.6405+0.2401)=0.188 XTLB(0) =(0.363+0.167)×0.188/(0.363+0.167+0.188) =0.1388 Xff1(0)=XL3(0)+XTLB(0)=0.8166+0.1388=0.9554

第 9 页 共 47 页

Iff1(0)*=E(0)/Xff1(0)=1.05/0.9554=1.099 Iff1(0)=Iff1(0)*IB=1.099×0.502=0.552KA

3.2.2 d2发生短路时流过断路2

(1)最大运行方式正序短路电流

Xff2=XdT+XL3=0.18255+0.2722=0.45475

Id2·max*=E/Xff2=1.05/0.45475≈2.309 Id2·max=Id2·max*IB=2.309×0.502≈1.159KA

(2)最小运行方式两相短路正序短路电流

X2 =(XL1+XL2)×XL3/( XL1+XL2+ XL3)= XL3/2=0.1361 Xff2=Xd1+X2=0.18255+0.1361=0.31865 If(3)*= E/2Xff1=1.05/2×0.31865=1.6475 If(3)=If(3)*IB=3.295×0.502=0.827KA

If(2)*=1.732E/4Xff1=1.732×1.05/4×0.31865=1.429 流过断路器1、2、3、4、5和6的短路电流为: If(2)=If(2)*IB=1.429×0.502=0.7163KA

(3)最大运行方式两相短路零序短路电流,如图3.2.2示

图3.2.2短路等值电路

XBL(0) =XL1(0)×XTB(0)/(XL1(0))+XTB(0))=0.4536×0.2401/(0.4536+0.2401)=0.157 XTL(0) =(XL4(0)+XT8(0))×XTC(0)/(XL4(0)+XT8(0)+XTC(0))=0.188 XLB(0) =(XL2(0)+XBL(0))×XTL(0)/(XL2(0)+XTBL(0)+XTC(0))=0.138 Xff2(0) =(XL3(0)+XT(0))×XLB(0)/(XL3(0)+XT(0))+XLB(0))=0.1208 Iff2(0)*=E(0)/Xff2(0)=1.05/0.1208=8.692 Iff2(0)=Iff2(0)*IB=8.692×0.502=4.3634KA

第 10 页 共 47 页