Ud%SB*=15/100*100/360=0.042 100SeUd%SB*=13/100*100/260=0.05 X4=

100SeUd%SB*=14.45/100*100/63=0.229 X8=X9=

100SeSB100架空线:X5=120*0.4*=48*=0.099

UB22202SB100 X6=100*0.4*=40*=0.083 22UB220SB100 X7=150*0.4*=60*=0.124 22UB220 X2=

X1+X2=0.014+0.042=0.056

X3+X4=0.022+0.05=0.072

X10=X5*X6/(X5+X6+X7)=0.099*0.083/(0.099+0.083+0.124)=0.027 X11=X5*X7/( X5+X6+X7)=0.04 X12= X6*X7/( X5+X6+X7)=0.034

转移电抗:X13=( X1+X2)+ X10=0.056+0.027=0.083 X14= (X3+X4 )+ X11=0.040+0.072=0.112 X15= X12=0.034

X16=X13+X15=0.083+0.034=0.117 X17=X14+X15=0.146

Se=0.24 SBSe Xjs17= X17* =2.102

SB计算电抗:Xjs16= X16*

查表得:Is16=4.526 Is17=0.488 I16= Is16*

SE=4.526*(4*300/0.85)/(1.732*220)=16.77 3UBSE=0.488*(6*240/0.875)/ (1.732*220)=2.108 3UBI17= Is17*

所以:I1= I16+ I17=18.878

d2点短路:

转移电抗:

X18=X13=0.083 X19=X14=0.112 X20=0.034+0.1145=0.149

X21= X18+ X20=0.083+0.149=0.232 X22=X19+X20=0.112+0.149=0.261 Xjs21= X21*

Se=0.232*2.0514=0.476 SBXjs22= X22*

Se=0.261*14.397=3.758 SB查表得:Is21=2.25 Is22=0.275

I21= Is21*

SE=2.25*(4*300/0.85)/(1.732*35)=52.4 3UBSE=0.275* (6*240/0.875)/ (1.732*35)=7.47 3UBI22= Is22*

所以:I2= I21+ I22=52.4+7.47=59.87

短路计算总结:

短路点 d1 d2

基准容量 100MW 100MW

基准电压

转移电抗 X16=0.017

220KV X17=0.146

X21=0.232

35KV X22=0.261

计算电抗 Ijs16=0.24

Ijs17=2.102 18.878 Ijs21=0.476

Ijs22=3.758 59.87

短路电流

4.主要电气设备的选择和校验

4.1断路器的选择

断路器型式的选择:除需满足各项技术条件和环境条件外,还考虑便于安装调试和运行维护,并经技术经济比较后才能确定。电压35及35kV一下的电网一般选用少油断路器,电压35—220kV电网,可选用SF6,空气或少油断路器,330及330KV以上用SF6或空气断路器。 断路器选择的具体技术条件如下:

(1)电压:Ug≤UN Ug---电网工作电压, UN---断路器的额定电压 (2)电流:Igmax≤IN Igmax---最大持续工作电流,IN ---断路器的额定电压

(3)开断电流:Ipt≤INbr

Ipt---断路器实际开断时间t秒的短路电流周期分量;INbr ---断路器额定开断