if k==N0,break;end for k3=k1:N0 for k2=k1:N1

J(k3,k2)=J(k3,k2)-J(k3,k)*J(k,k2); end

J(k3,k)=0; end else

for k3=k1:N0 for k2=k1:N1

J(k3,k2)= J(k3,k2)-J(k3,k)*J(k,k2); end

J(k3,k)=0; end end end

for k=3:2:N0-1 L=(k+1)./2;

e(L)=e(L)-J(k,N); k1=k+1;

f(L)=f(L)-J(k1,N); end

for k=3:N0

DET=abs(J(k,N)); if DET>=pr IT2=IT2+1; end end

ICT2(a)=IT2; ICT1=ICT1+1; end

%用高斯消去法解“w=-J*V” disp('迭代次数'); disp(ICT1);

disp('没有达到精度要求的个数'); disp(ICT2); for k=1:n

V(k)=sqrt(e(k)^2+f(k)^2);

shita(k)=atan(f(k)./e(k))*180/pi; E(k)=e(k)+f(k)*j; end

disp('各节点的实际电压标么值E为(节点号从小到大排列):'); disp(E);

19

disp('各节点的电压大小V为(节点号从小到大排列):'); disp(V);

disp('各节点的电压相角时shita为(节点号从小到大排列):'); disp(shita); for p=1:n C(p)=0; for q=1:n

C(p)=C(p)+conj(Y(p,q))*conj(E(q)); end

S(p)=E(p)*C(p); end

disp('各节点的功率S为(节点号从小到大排列):'); disp(S);

disp('各条支路的首端功率Si为(顺序同您输入B1时一样):'); for i=1:nl

if B1(i,6)==0

p=B1(i,1);q=B1(i,2); else p=B1(i,2);q=B1(i,1); end

Si(p,q)=E(p)*(conj(E(p))*conj(B1(i,4)./2)+(conj(E(p)*B1(i,5))-conj(E(q)))*conj(1./(B1(i,3)*B1(i,5)))); disp(Si(p,q)); end

disp ('各条支路的末端功率Sj为(顺序同您输入B1时一样):'); for i=1:nl

if B1(i,6)==0

p=B1(i,1);q=B1(i,2); else p=B1(i,2);q=B1(i,1); end

Sj(q,p)=E(q)*(conj(E(q))*conj(B1(i,4)./2)+(conj(E(q)./B1(i,5))-conj(E(p)))*conj(1./(B1(i,3)*B1(i,5)))); disp(Sj(q,p)); end

disp('各条支路的功率损耗DS为(顺序同您输入B1时一样):' ); for i=1:nl

if B1(i,6)==0

p=B1(i,1);q=B1(i,2); else p=B1(i,2);q=B1(i,1); end

DS(i)=Si(p,q)+Sj(q,p); disp(DS(i)); end

四、实验数据:

电力系统接线图如图1所示,根据图中数据可得B1、B2和X矩阵:

20

P5=5j0.0151:1.05③j0.250.8+j0.30j0.250.04+j0.25②1.05:1j0.03①⑤U5=1.052+j13.7+j1.30.1+j0.35U1=1.05δ1=0°j0.25j0.25④1.6+j0.8

图1 电力系统接线图

B1=[1 2 0.03i 0 1.05 0;2 3 0.08+0.3i 0.5i 1 0;2 4 0.1+0.35i 0 1 0;3 4 0.04+0.25i 0.5i 1 0;3 5 0.015i 0 1.05 1];

B2=[0 0 1.05 1.05 0 1;0 3.7+1.3i 1 0 0 2;0 2+1i 1 0 0 2;0 1.6+0.8i 1 0 0 2;5 0 1.05 1.05 0 3]; X=[1 0;2 0;3 0;4 0;5 0];

五、实验过程

1.认真阅读源程序,建立matlab的M程序,输入潮流计算程序。

2.输入实验数据,用B1、B2和X矩阵代替B1、B2和X输入语句并调试程序。 B2矩阵

B2(i,1)为节点所接发电机功率P; B2(i,2)为节点的负荷功率SL; B2(i,3)为节点电压的初值;

B2(i,4)为PV节点电压的给定值;

B2(i,5)为节点所接的无功补偿设备容量;

B2(i,6)为节点的分类号:1-平衡节点,2-PQ节点,3-PV节点。 3. 运行程序,输入节点数n=5、支路数n1=5、输入平衡母线节点号:isb=1、输入误差精度:pr=0.00001,进行计算。 六、要求

认真书写实验报告,画出网络接线图,在图上标出各节点电压和各支路功率,并用箭头标出各支路功率方向。

附件:计算参考结果 请输入节点数:n=5 请输入支路数:nl=5

请输入平衡母线节点号:isb=1 请输入误差精度:pr=0.00001 导纳矩阵Y= Column 1

0 -33.33333333333334i 0 +31.74603174603175i

21

0 0 0 Column 2

0 +31.74603174603175i 1.58459249980427 -35.73785857758467i -0.82987551867220 + 3.11203319502075i -0.75471698113208 + 2.64150943396226i 0 Column 3

0 -0.82987551867220 + 3.11203319502075i 1.45390047967064 -66.98082109846432i -0.62402496099844 + 3.90015600624025i 0 +63.49206349206349i Column 4

0 -0.75471698113208 + 2.64150943396226i -0.62402496099844 + 3.90015600624025i 1.37874194213052 - 6.29166544020251i 0 Column 5

0 0 0 +63.49206349206349i 0 0 -66.66666666666667i 迭代次数 5

没有达到精度要求的个数

7 8 8 6 0

各节点的实际电压标么值E为(节点号从小到大排列): Column 1

1.05000000000000 Column 2

1.03351793598970 - 0.07738281826869i Column 3

1.02600730614413 + 0.33047260236366i Column 4

0.85915374471705 - 0.07182065733577i Column 5

0.97461502463687 + 0.39067320582818i

各节点的电压大小V为(节点号从小到大排列): Columns 1 through 3

22

1.05000000000000 1.03641083773551 1.07791610674215 Columns 4 through 5

0.86215042996073 1.05000000000000

各节点的电压相角时shita为(节点号从小到大排列): Columns 1 through 3

0 -4.28193006920383 17.85352958577940 Columns 4 through 5

-4.77851050308856 21.84331901623337 各节点的功率S为(节点号从小到大排列): Column 1

2.57942727562302 + 2.29940213367660i Column 2

-3.70000000000000 - 1.30000000000000i Column 3

-2.00000000000000 - 1.00000000000000i Column 4

-1.59999999999999 - 0.79999999999996i Column 5

5.00000000000000 + 1.81308400259910i

各条支路的首端功率Si为(顺序同您输入B1时一样): 2.57942727562302 + 2.29940213367659i -1.27736037177247 + 0.20317048483099i 0.15678764739549 + 0.47131477149638i 1.58454630565503 + 0.67255630190799i 5.00000000000000 + 1.81308400259910i

各条支路的末端功率Sj为(顺序同您输入B1时一样): -2.57942727562302 - 1.97448525632736i 1.41545369434497 - 0.24433316462154i -0.13381873506914 - 0.39092357835416i -1.46618126493085 - 0.40907642164580i -5.00000000000000 - 1.42822313728644i

各条支路的功率损耗DS为(顺序同您输入B1时一样): -0.00000000000000 + 0.32491687734924i 0.13809332257250 - 0.04116267979055i 0.02296891232635 + 0.08039119314222i 0.11836504072417 + 0.26347988026219i 0.00000000000000 + 0.38486086531266i

23


电力系统分析实验指导书(5).doc 将本文的Word文档下载到电脑 下载失败或者文档不完整,请联系客服人员解决!