安徽华电六安发电有限公司二期工程
(2×660MW)机组
MIS机房建设施工
技术标书
二○一二年八月
MIS机房建设设计方案
目 录
一、工程概况 .......................................................................................................................................... 3 二、设计规范 .......................................................................................................................................... 3 三、机房功能室划分 .............................................................................................................................. 4 四、机房工程设计目标和方案特色 ...................................................................................................... 4 五、机房区概述 ...................................................................................................................................... 5 六、机房设计方案概括 .......................................................................................................................... 6 6.1建筑装修 ........................................................................................................................................ 6 6.1.1地面 ......................................................................................................................................... 6 6.1.2吊顶 ......................................................................................................................................... 7 6.1.3墙面 ......................................................................................................................................... 8 6.2电气部分 ........................................................................................................................................ 9 6.2.1照明系统 ................................................................................................................................. 9 6.2.2配电系统 ................................................................................................................................. 9 6.3空调部分 ........................................................................................................................................ 9 6.4 UPS部分 ...................................................................................................................................... 10 七、机房供配电工程设计方案 ............................................................................................................ 11 7.1供电类别负荷等级及线制 .......................................................................................................... 11 7.2供电质量要求 .............................................................................................................................. 11 7.3供电的计算容量 .......................................................................................................................... 12 7.4机房低压配电系统设计方案 ...................................................................................................... 13 7.5机房照明工程设计方案 .............................................................................................................. 14 7.6机房内电源插座的配置 .............................................................................................................. 16 八、机房防浪涌过压保护和接地工程设计方案 ................................................................................ 17 8.1防浪涌过压保护方案 .................................................................................................................. 17 8.2机房接地系统技术方案 .............................................................................................................. 18 九、空调新风排风工程设计方案 ........................................................................................................ 19 9.1冷负荷计算及机房环境特点 ...................................................................................................... 19 9.2机房专用空调与舒适性空调的区别 .......................................................................................... 21 9.3产品选型及技术特点 .................................................................................................................. 23 十、机房集中监控设计方案 ................................................................................................................ 26 10.1系统组成结构 ............................................................................................................................ 26 10.2机房监控方案 ............................................................................................................................ 32 10.2.1配电监控: ......................................................................................................................... 32 10.2.2配电柜监控 ......................................................................................................................... 33 10.2.3UPS检测系统 ..................................................................................................................... 34 10.2.4空调监控 ............................................................................................................................. 35
1
MIS机房建设设计方案
10.2.5漏水监控 ............................................................................................................................. 36 10.2.6温湿度检测系统 ................................................................................................................. 38 10.2.7门禁监控系统 ..................................................................................................................... 39 10.2.8电话报警子系统电子邮件及警灯报警 ............................................................................. 41 十一、施工组织及技术服务 ................................................................................................................ 42 11.1施工计划及组织 ........................................................................................................................ 42 11.1.1 施工计划 ............................................................................................................................ 42 11.1.2施工组织 ............................................................................................................................. 43 11.2工程进度控制管理和质量体系 ................................................................................................ 45 11.2.1工程进度控制进度控制 ..................................................................................................... 45 11.2.2质量体系 ............................................................................................................................. 48 11.3验收方案建议 ............................................................................................................................ 55 11.4技术支持与售后服务承诺 ........................................................................................................ 56 十二、设计图纸目录 ............................................................................................................................ 58 十三、预算报价 .................................................................................................................................... 58 十四、结束语 ........................................................................................................................................ 58 十五、附录-部分工程案例 ................................................................................................................... 59
2
MIS机房建设设计方案
一、工程概况
(一) 工程名称 安徽华电六安电厂二期2×660MW超超临界机组机房工
程
(二) 工程概况
机房工程位于生产综合楼南一楼,机房层高为4.2m,规划设计面积约71m2。 主要划分为主机房(59.5 m2)、UPS室(11.5 m2)两个区域。电池室(不考虑装 修,但要做漏水监测及安装UPS电池组)位于生产综合楼南一楼。
(三) 工程承包范围
工程承包范围包括装饰工程、供配电工程、空调及新风系统、环境与动力设备集成监控工程、UPS、综合布线、防浪涌过压与接地及灾害防护等部份。
二、设计规范
该工程按机房使用要求进行设计,并遵守以下规范和要求。 <<计算站场地技术条件>> (GB2887-89) <<计算站场地安全要求>> (GB9361-88) <<电子计算机机房设计规范>> (GB50174-94) <<建筑内部装修设计防火规范>> (GB50222-95) <<供配电系统设计规范>> (GB50052-92) <<建筑物防雷设计规范>> (GB50057-94) 机房施工要求遵守规范:
<<电子计算机机房工程施工及验收规范>> (ST/t30003-93) <建筑装饰工程施工及验收规范>> (JGJ73-91) <<通风与空调工程施工及验收规范>> (GB50243-97) <<建筑电气工程施工质量验收规范>> (GB50303-2002)
3
MIS机房建设设计方案
三、机房功能室划分
四、机房工程设计目标和方案特色
根据上述设计依据,遵照工程设计基本原则(先进性、安全性、实用性、可扩展性和经济合理性),按照计算机机房建设要求,参照现代互联网数据机房设计案例,计算机机房的设计方案应严格区别于商场、文体、公寓等共用建筑的室内设计风格。
作为信息系统的核心场地,应有自己的建设目标和特点。该机房工程设计目标应是符合现代IT行业需求,达到优良级质量标准。实现目标:一是必须满足机房内计算机、服务器等电子设备稳定可靠运行环境;二是为工作在机房内科技人员,提供舒适、高效、健康的工作环境;三是具有便捷易维护的使用环境。为此,了解业主使用需求,从各功能室的划分,室内装饰风格,材料选型,设备配套,施工程序和工艺质量要求等诸多方面进行了工程方案设计,使该机房建设具有如下特色:
A.高可靠性一体化供配电方案
根据该机房为网络信息中心的使用需求,是重要的信息交换场地,本方案设计二类供电方式、二级供电质量、三相五线制和单相三线制的供电方式,即TN-S
4