access to the Experion website and priviledges/access that allow them to download all current patches etc.
Installation for each patch/upgrade will be described by it’s accompanying SCN (Software Change Notice) below is a table for record purposes and should be filled in when each patch is applied.
? PERC Firmware 6.3.0-0001,A12 ? MS Hotfix ? Controller Patch1 ? Server Patch 1 ? HMIWeb Patch 2
? System Management Patch 2
? ExperionPKS.R400.Server.Patch102.PAR1-J4C742
? ExperionPKS_R400.1_HMIWeb_Patch_6_0_143_5200_PAR1-JD8OA7
6. 安装中文
Change System Locale to Chinese (Simplified, PRC). 将系统改为简体中文
unlock logon for mngr. 解锁登陆mngr用户,可以参考下面截屏 入下命令
Run gpedit.msc secpol.msc
? log on as mngr account, open Regional and Language Options, change
formats & location to Chinese & China.
? log on as user-defined administrator account, open Regional and Language
Options, change formats & location to Chinese & China, then change the system locale to Chinese (Simplified, PRC). ? reboot.
? Copy to reserved accounts ( check ―Defalut user account‖ ). ? lock logon for mngr
? Open Registry Editor, navigate to
HKEY_LOCAL_MACHINE\\SOFTWARE\\Honeywell\\Experion PKS Server
? Add a string value SQLCollation and modify its data as Chinese_PRC_CI_AS. 如下图
所示
? Bring the server down to Database Only level.
? Run command prompt as administrator , type installsqlobject EMSEvents /c 如下图所
示
详细设置步骤请参考附件
Chinese Setting
7. 检查Dongle 和License
中文的安装很容易造成License的丢失,需要动作Change License。 否则 Server Redundancy 中的 hdwbld redun.hdw 不能执行。
8. Configuring Experion server redundancy
(1) Choose Start > All Programs > Honeywell Experion PKS > Server > Start-Stop Experion Server.
The Experion PKS Server dialog box appears.
Click the stop button.
If prompted, click Yes to confirm the action.
Wait for the server to change to stop state. It may take several minutes for the Experion server to stop.
(2)分别在两台服务器 (PKSServerA和PKSServerB)上, choose Start > All Programs > Honeywell Experion PKS > Server > Diagnostic Tools > Experion Command Prompt to open the Experion Command Prompt window.
在“Experion Command Prompt”命令行窗口中输入命令:hdwbld redun.hdw 并回车 执行以上命令后,如果窗口提示errors为0,那么表示命令执行成功,重启两台服务器,当两台服务器重启后会自动互相识别,并分别变为“Primary”和“Backup”。 两台冗余服务器互相识别出主、备后,需要对这两台服务器进行同步配置,如下:
―Synchronizing the server databases‖ on page 115
―Synchronizing the Engineering Repository database‖ on page 117 ―Synchronizing the Enterprise Model database‖ on page 118
For more information, go to Knowledge Builder: Experion R400 > Configuration> Server and Client Configuration Guide > Configuring and monitoring a redundant server system.
9. limit SQL Server memory usage
10. Setting up time synchronization
时钟源的配置分为三种情形,即主时钟源(Authoritative Root Server),备份时钟源(secondary NTP server)以及时钟同步客户端(NTP clients,例如所有的操作站均是时钟同步的客户端),还有控制器的时钟同步配置,详细步骤如下:
Setting up time synchronization in a workgroup without an external time source checklist
(a)Setting up the authoritative root server
This topic describes setting up your primary Experion server as the authoritative root server in your time hierarchy.
To set up an authoritative root sever
1 In Windows Explorer, go to C:\\program files\\Honeywell\\Experion
PKS\\Utilities\\NTPSetup.
2 Double-click the NTPConfig.exe file. The NTP Configuration dialog appears. 3 Click Setup Authoritative Root Server.
Several screens appear while the configuration is applied. No input is
required.
4 Click Exit.
(b)Setting up the secondary NTP server
This topic describes setting up your secondary Experion server as your secondary NTP server in your time hierarchy. Prerequisites
? You need to know the IP address or computer name of the authoritative root server. If
you use a computer name, it must resolve to an IP address using Host, DNS, or other
resolution service.
To set up your secondary NTP server
1 In Windows Explorer, go to C:\\program files\\Honeywell\\Experion
PKS\\Utilities\\NTPSetup.
2 Double-click the NTPConfig.exe file. The NTP Configuration dialog appears. 3 Click Setup Secondary Server.
The NTP Server Information dialog box opens.
4 In the Up-Stream Time Source box, type the IP address or computer name of the authoritative root server. 5 Click OK. 6 Click Exit.
(c)Setting up NTP clients in a workgroup without an external time source
This topic describes how to set up NTP clients on such as Console Stations and Flex Stations. Prerequisites
? You need to know the IP address or computer name of the authoritative root server and the secondary server. If you use a computer name, it must resolve to an IP address using Host, DNS, or other resolution service.
? If you are setting up clients on Windows XP Professional, you must use the computer name of the authoritative root server and the secondary server. The computer name must resolve to an IP address.
To set up NTP clients
1 In Windows Explorer, go to C:\\program files\\Honeywell\\Experion
PKS\\Utilities\\NTPSetup.
2 Double-click the NTPConfig.exe file. The NTP Configuration dialog appears. 3 Click Change/Configure Client.
The NTP Server Information dialog box opens.
4 In the First NTP Server box, type the IP address or computer name of the
authoritative root server.
If this client is using Windows 7, type the computer name of the authoritative
root server.
5 In the Second NTP server box, type the IP address or computer name of
the secondary server.
If this client is using Windows 7, type the computer name of the secondary
server.
6 Click OK. 7 Click Exit.
(d) Setting up control hardware to receive time from an NTP server in a workgroup without an external time source
This topic describes setting up C300 controllers to receive time from your NTP servers
(Experion servers). Prerequisites
? You need to know the IP address or computer name of the authoritative root server and the secondary server. If you use a computer name, it must resolve to an IP address using Host, DNS, or other resolution service.
To set up control hardware