i)计算电流
Kx = 0.7,Cosφ = 0.5
Ijs = Kx×ΣPe/(1.732×Ue×Cosφ) = 0.7×150/(1.732×0.38×0.5) = 319.07A ii)选择导线 按允许电压降:
S = Kx×Σ(PL)/C△U = 0.7×225/(77×5) = 0.41mm2 选择VV3×240+2×120 iii)选择电气设备
选择分配箱进线开关为DZ10-600/3 ,其脱扣器整定电流值为Ir = 480A。 (16)分2进线及进线开关的选择 i)计算电流
Kx = 0.7,Cosφ = 0.5
Ijs = Kx×ΣPe/(1.732×Ue×Cosφ) = 0.7×149/(1.732×0.38×0.5) = 316.94A ii)选择导线 按允许电压降:
S = Kx×Σ(PL)/C△U = 0.7×129/(77×5) = 0.23mm2 选择VV3×240+2×120iii)选择电气设备
选择分配箱进线开关为DZ10-600/3 ,其脱扣器整定电流值为Ir = 480A。 (17)分3进线及进线开关的选择 i)计算电流
Kx = 0.7,Cosφ = 0.5
Ijs = Kx×ΣPe/(1.732×Ue×Cosφ) = 0.7×111/(1.732×0.38×0.5) = 236.11A ii)选择导线 按允许电压降:
S = Kx×Σ(PL)/C△U = 0.7×72/(77×5) = 0.13mm2 选择VV3×185+2×95 iii)选择电气设备
选择分配箱进线开关为DZ10-600/3 ,其脱扣器整定电流值为Ir = 480A。 (18)分4进线及进线开关的选择 i)计算电流
Kx = 0.7,Cosφ = 0.5