22.08 21.09 2.70 4.60 80 25.87 21.09 2.70 0.00 80 27.27 21.09 0.82 0.00 80 27.70 21.09 3.61 2.10 80 30.66 21.09 2.03 2.10 80 32.81 21.09 2.90 0.00 80 34.31 21.09 2.90 0.80 80 80 0.519 80 0.519 80 0.519 80 0.519 80 0.519 80 0.519 80 0.519 4.25 3.79 4.25 1.40 4.25 0.42 4.25 2.97 4.25 2.15 4.25 1.51 4.25 1.92 2.44 0.06 2.44 0.29 2.44 0.18 2.44 0.75 2.44 0.53 2.44 0.32 2.44 0.32 2.44 0.32 2.44 0.35 2.44 0.49 1.59 0.03 1.59 0.08 25.87 27.27 27.70 30.66 32.81 34.31 36.23 36.29 36.58 36.76 37.51 38.03 38.35 38.67 39.00 39.35 39.84 39.87 39.95 36.23 21.09 0.50 0.00 100 80 0.119 36.29 21.09 2.40 0.00 100 80 0.119 36.58 21.09 1.52 0.00 100 80 0.119 36.76 21.09 3.19 3.10 100 80 0.119 37.51 21.09 1.33 3.10 100 80 0.119 38.03 21.09 2.70 0.00 100 80 0.119 38.35 21.09 2.70 0.00 100 80 0.119 38.67 21.09 2.70 0.00 100 80 0.119 39.00 21.09 2.95 0.00 100 80 0.119 39.35 21.09 3.05 1.10 100 80 0.119 39.84 21.09 0.80 0.00 125 80 0.038 39.87 21.09 2.11 0.00 125 80 0.038 计算结果:
所选作用面积:160平方米
- 25 -
总流量:21.09 L/s
平均喷水强度:7.54 L/min.平方米 入口压力:39.95 米水柱
计算用图如下:
- 26 -
- 27 -
图4.2 自喷系统计算图
局部损失取沿程损失的20%,,故管段内的总损失为
∑h=1.2?329.7=395kPa
⑧系统所需水压,按下式计算:
H=∑h+Z (4.9)
式中 H ——系统所需水压,kPa;
∑h——管道沿程和局部损失的累计值,kPa;
Z ——最不利点出喷头与消防水池的最低水位的高程差,kPa。
H=395+(5.2+4.5+3.9+3.9)?10=600kPa
⑷加压设备的选择
根据上述计算结果,自动喷水灭火系统所需压力为60mH2O,所需供水量为25L/s,故选择加压泵为XBD6/30-SLH(参04S204),流量为25L/S,压力为0.6MPa,功率为37KW。
4.3.3消防水池容积的计算
水池容积
Vc=Qx?Tx×3600/1000=20×2×3600/1000+25×1×3600/1000=234m3
取240m3。 4.4 室外消防给水系统 4.4.1 室外消防给水管网
室外消防管网布置成环状,室外消防管网从两条市政给水管引入。从消防管网引入室内消防水池的引入管为两条,管径DN100。当其中一条进水管发生故障时,另一条能保证进水量。
市政管网最低压力0.25MPa,满足要求。 4.4.2 室外消火栓
室外消火栓的数量经计算确定,室外消防流量20L/s,故采用2个室外消火栓。沿建筑周边均匀布置,距建筑物外墙不小于5m。
由于地处北方,考虑到防冻要求,采用地下式消火栓。安装在消火栓井内,井采用保温井盖。
- 28 -
4.5 管材
室内消火栓给水系统管材采用内外壁热镀锌钢管,具有强度高、承受压力大、抗震性能好、长度大、加工安装方便的优点。卡箍或丝扣连接。
自动喷水灭火系统采用内外壁热浸镀锌钢管,以防止管道锈蚀尔阻塞喷嘴喷口。管道系统的连接,管径〈100mm是采用丝扣连接,?100mm时采用沟槽式卡箍连接。 管道的配件采用该类管材相应的专用配件。