风力发电工程初步设计内容深度规定
目 录
1总的部分 ..........................................................2
1.1概述 ...............................................................................................................................................2 1.2风电场升压站站址概况 ...............................................................................................................2 1.3主要设计原则及存在的问题 .......................................................................................................2 1.4主要技术经济指标 .......................................................................................................................2
2 电力系统.........................................................1
2.1 电力系统 ......................................................................................................................................1 2.2 系统继电保护及安全自动装置 ..................................................................................................1 2.3系统通信 .......................................................................................................................................1 2.4站内通信 .......................................................................................................................................1 2.5调度自动化 ...................................................................................................................................1
3 升压站部分........................................................1
3.1 电气一次部分 ..............................................................................................................................2 3.2 电气二次部分 ..............................................................................................................................2 3.3电缆设施 .......................................................................................................................................3
4 站区总布置及交通运输..............................................3
4.1站区总平面布置及竖向布置 .......................................................................................................3 4.2交通运输 .......................................................................................................................................4
5土建部分 ..........................................................5
5.1工程规模及工程等级 ...................................................................................................................5 5.2站区建筑 .......................................................................................................................................5 5.3站区结构设计 ...............................................................................................................................6
6采暖及通风部分 ....................................................7
6.1设计原则 .......................................................................................................................................7 6.2采暖方案及设备选型 ...................................................................................................................7 6.3空调方案及设备选型 ...................................................................................................................8 6.4通风方案及设备选型 ...................................................................................................................8
7水工部分 ..........................................................8
7.1水源及用水量 ...............................................................................................................................8 7.2供水方案及给水系统 ...................................................................................................................8 7.3排水系统 .......................................................................................................................................8 7.4污水处理 .......................................................................................................................................8
8消防部分 ..........................................................8
风力发电工程初步设计内容深度规定
8.1 概述 .............................................................................................................................................8 8.2 消防给水 .....................................................................................................................................9 8.3 其他消防措施及消防供电 .........................................................................................................9
9附图 .............................................................11 10 专题报告........................................................12
10.1综合控制楼方案优化和比选 ................................................................................................... 12
附表一 风电场综合控制楼生产、非生产建筑面积........................13
1总的部分
升压站初步设计文件编制应按照《国家电网公司输变电工程初步设计内容深度规定 第2部分:变电站》(Q/GDW 166.2-2007)规定执行。 1.1概述
描述工程概况,工程所处的地理位置、行政隶属关系、风电场的规划、本期建设容量、升压站的规划等。 1.2风电场升压站站址概况
应说明站址的自然条件、处于风电场的位置、站址标高与洪水位的关系等。 1.3主要设计原则及存在的问题
应描述各系统的技术方案及站址存在的问题。 1.4主要技术经济指标
序号 1 2 3 4 5 6 7 项目名称 静态投资 动态投资 综合控制楼 站区内总建(构)筑面积 站区围墙内占地面积 绿化面积 站区征地面积 单位 万元 万元 M M hm M hm2 2222数量 技术经济指标
风力发电工程初步设计内容深度规定 8 9 10 11 12 钢材消耗量 木材消耗量 水泥消耗量 站内道路 站区土石方量:挖方、填方 T M T M M 323 2 电力系统
2.1 电力系统
应根据批准的接入系统报告及审批意见简要描述接入系统的结论,如出线回路数、导线截面积、线路长度、对端变电所的简要情况。 系统对电气设备参数要求及不确定事项的阐述。 无功补偿的要求及其他有关要求。 不再论述建设必要性及电力需求。 2.2 系统继电保护及安全自动装置
应根据接入系统(二次部分)审查意见和规程、规范编写,设置继电保护装置和检测装置等; 根据接入系统审查意见,是否设置安全自动装置,或预留费用等。 2.3系统通信
应根据接入系统(二次部分)审查意见编写。 2.4站内通信
应根据接入系统(二次部分)审查意见和站内有关通信设计编写。 2.5调度自动化
应根据接入系统(二次部分)审查意见编写。
3 升压站部分 应满足变电所设计初步设计内容深规定的要求。升压站型式,宜采用敞开式配电装置,当环境温度低于-40℃或滨海升压站时(环境污染特别严重地区),可选用全封闭组合电气GIS。
1
风力发电工程初步设计内容深度规定
3.1 电气一次部分
应满足GB 50059 35~110KV 变电所设计规范的规定。
3.1.1电气主接线
电气主接线应包括两部分,其一是升压站部分,其二是35KV集电线路部分,
主接线应进行多方案比较,确定推荐方案。 3.1.2短路电流计算及主要设备选择
应根据系统给定的阻抗,计算集电线路电压等级和出线电压等级的短路电流水平;确定主要设备选型和导体选择的原则。 3.1.3绝缘配合及过电压保护
应根据不同的电压等级、海拔高度、湿度、污染等级选择设备的内绝缘和外绝缘;根据设备布置情况、电压等级配置雷电过电压保护装置;330KV及以上的电压等级升压站应考虑操作过电压保护。 3.1.4防雷接地
应说明升压站防直击雷保护方式。
根据土壤电阻率设计接地网。当土壤电阻率过高。应进行专题论证;对人员经常出入的地方,计算跨步电压和接触电压,使跨步电压和接触电压降低到安全范围内;电气设备、设备支架、杆塔均要有效接地;对接地材料及材料防腐应予以说明,并满足规定的要求 3.1.5配电装置及电气设备布置
升压站的布置、集电线路配电装置布置、无功补偿布置、站用电布置、继电保护室、蓄电池、直流系统等布置。 3.1.6站用电及照明
应说明站用电的配置接线、消防用电的接线、照明电源及应急照明等。 3.2 电气二次部分
应说明风电场的控制方式、监测方式、主控制室与继电保护室的规划、建设等。
3.2.1计算机监测系统
应说明升压站的二次设备(包括控制、保护、信号、测量、自动装置、远动终端等)和应用的自动控制技术等功能。
2
风力发电工程初步设计内容深度规定
3.2.2 直流系统 3.2.2.1 直流电源
应说明直流系统电压等级、蓄电池组数及容量、充电方式、蓄电池布置、直流屏布置等。
3.2.2.2不停电电源(UPS)系统
应说明UPS的构成及容量、接入UPS的负荷等。 3.2.3元件保护及自动装置
元件保护应按《继电保护和安全自动装置设计技术规程》设置,说明元件保护原则,分述主变压器、35kV(或10KV )线路保护、35kV(或10KV )动态无功补偿装置保护、35kV(或10KV )站用变压器保护;无功补偿装置自动投切方案、站用备用电源自动投入方案。 3.2.4安全监视系统
应说明安全监视系统功能定位及作用,监视范围及具体摄像设备布点方案。 3.3电缆设施
电缆设施应以沟道为主,原则上不宜设置电缆隧道。如果集电线路采用35KV电缆进入35KV配电装置,局部可设电缆隧道。电缆原则上选用铜芯,考虑部分电缆抗干扰问题,应设置必要的防火设施。
4 站区总布置及交通运输 4.1站区总平面布置及竖向布置 4.1.1 全站总体规划
应结合场地自然条件和地形特点,进行站区总平面规划; 应说明地形图所采用的坐标、高程系统及站址经纬度。 4.1.2站区总平面布置
a)站区的总平面布置应根据风电场的总体规划进行多方案布置比较,推荐出技术经济合适的方案,提供总平面布置图。
b)总平面布置应结合站区的总体规划及电气工艺的要求进行布置。应结合工程自然条件和特点,满足安全、防火、运行、检修、交通运输、环境保护各方面的要求 ,尽量压缩土地,使全站的用地控制在最小的范围内。
3