六.指令语句表
1 2 3 4 5 6 7 8 9 10 11 12 13 14
LD OR AND NOT OUT TIM LD OR ANDNOT OUT TIM LD OR LD NOT AND NOT 0000 1000` 0001 1000 000 #0020 0002 1001 0003 1001 001 #0020 1000 1001 TIM000 TIM001
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
OR NOT AND LD OUT LD ANDNOT LD NOT ORNOT ANDLD OUT LD OR ANDNOT OUT TIM LD OR ANDNOT OUT TIM LD OR LDNOT ANDNOT ORNOT ANDLD OUT LD ANDNOT LDNOT ORNOT ANDLD OUT LD ANDNOT LDNOT ORNOT ANDLD OUT LD OR ANDNOT TIM006 1002 1000 0004 TIM000 TIM006 1004 0006 1005 0007 1005 002 #0020 0008 1006 0009 1006 003 #0020 1005 1006 TIM002 TIM003 TIM006 1007 1005 0010 TIM002 TIM006 1008 1006 0011 TIM003 TIM006 1009 0012 1010 0013
56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 OUT TIM LD OR ANDNOT OUT TIM LD OR LDNOT ANDNOT ORNOT OUT LD ANDNOT LDNOT ORNOT ANDLA OUT LD ANDNOT LDNOT ORNOT ANDLD OUT LD OR OR OR OR OR ANDNOT OUT TIM 1010 004 #0020 0014 1011 0015 1011 005 #0020 1010 1011 TIM004 TIM005 TIM006 1012 1010 0016 TIM004 TIM006 1013 1011 0017 TIM005 TIM006 1014 1000 1001 1005 1006 1010 1011 TIM006 1015 006 #0200 七.程序调试
先将程序输入试验机,再用模拟信号调试,调试成功后再投入使用,再模拟调试时,我们最常用的是输入短接法调试。
用输入短接法调试程序
用一根导线将电”+”和PLC输入端的COM端短接;另用一根导线的一端接电源“-”,另一端做活动端。
将一根活动端与00000短接,观察到所对应的HL灯亮,然后将活动端与00001接通。
八.工作过程
当一号病房一号床位需要帮助时,他可以按下按钮即0000,他所在床位的继电器线圈就会得电,它的常开触点就会闭合,即1000闭合,然后TIM000同时开始计时,同时一号病房的等就会发亮,即1002得电,同时蜂鸣器也会想起,即1015得电,同时医护室所对应的病床的等也在闪烁,即1003得电。
当医护人员接到信号,他们可以按下复位按钮即0004,使信号停止呼叫。 然后等就熄灭,蜂鸣器也停止报警。 二号病房集散号病房工作原理同上。
当同时有多个人在呼叫时,医护人员如果来不及按复位按钮,则等会延时20S,20S后自动熄灭。
结束语
本系统主要以PLC为核心,经实验验证,表面呼叫及时、准确、可靠、可以满足医院的病房管理和护理要求,同时充实了病床呼叫系统的控制方式。利用可编程控制器控制,具有接线简单、编程直观、扩展容易等特点。当建筑物的层楼增加时,硬件接线上只需增加楼层,病房相应的输入信号。原来的接线不需改变,软件上只需增加相应楼层,房间,床位的功能,要改动的地方也较少。
谢 辞
经过几个月的查资料、整理材料、写作论文,今天终于可以顺利的完成论文的最后的谢辞了,想了很久,要写下这一段谢词,表示可以进行毕业答辩了,时