Chapter 1 Product Description 1

Chapter 1 Product Description

1.1 Introduction

The UPS JBUS/MODBUS adapter (hereinafter referred to as “adapter”) allows you to use your host monitoring

software to monitor your Emerson UPS and FLP field lighting power supply system (FLP for short) equipment through JBUS/MODBUS (RTU) protocol, to learn about the equipment operating status by acquiring the equipment electrical parameter data, operating data and alarm data.

Currently the adapter supports the UPS and FLP equipment listed in Table 1-1.

Table 1-1 UPS and FLP equipment supported by adpater

S/N. 1 2 3 4 5 6 7 8 9 10 11 Equipment UL33 UPS UH31 UPS UH11 UPS ITrust 2G UPS iTrust Adapt UPS 5/10/16/20kVA NXa UPS NXb UPS NXe UPS Hipulse U UPS 120/160/200/300/400 kVA FLP120/160/200/300/400 kVA NXr UPS Equipment series ITrust series NX series Hipulse U series FLP series NXr series 1.2 Specifications And Features

?Protocol: JBUS/MODBUS (RTU); ?Communication mode: RS485, RS232; ?Setting range of physical address: 1~31;

?Setting range of communication baud rate: 2400, 4800, 9600 (default), 19200bps; ?Communication data format: 1 start bit, 8 data bit, 1 stop bit, no parity check; ?CRC16 standard check mode, first high byte, then low byte; ?Hot-pluggable, easy to install.

1.3 Appearance And Hardware Description

Appearance

The adapter is a plug-in card, and should be plugged in the SNMP slot of the UPS and FLP. The adapter is shown in Figure 1-1.

UPS JBUS/MODBUS Adapter User Manual

2 Chapter 1 Product Description

Plug-in connectorDIP switchHost communication LEDEquipment communication LED Communication port

Figure 1-1 Adapter appearance

Hardware description

The printed board of the adapter is available in two sizes: 130mm (L) ×60mm (W) ×1.6mm (H) and 130mm (L) ×63mm (W) ×1.6mm (H); additionally, the former has a narrow opening at the plug-in connector. The former is

applicable to NX, NXr series UPS and iTrust Adapt UPS, while the latter is applicable to Hipulse U series UPS, FLP, and all iTrust series UPS except for iTrust Adapt UPS.

As shown in Figure 1-1, the adapter provides communication port, equipment communication LED, host communication LED, plug-in connector and DIP switch, which are described in Table 1-2.

Table 1-2 Hardware description

Name Communicaton port equipment communication LED (yellow) Host communication LED (green) Plug-in connector DIP switch Description Connects to the host computer, supports RS232 and RS485 communication modes OFF: power off ON: power on, but communication with UPS or FLP not established Flash slowly (once per 5s): communication with UPS or FLP failed Flash quickly (about once per 1s): communication with UPS or FLP is normal OFF: communication with host computer not established Flash: communication with host computer being normal Plug in the SNMP slot of the UPS or FLP, connect to the UPS or FLP Used to configure the basic parameters of the adapter ?

Warning

All external ports of the adapter must connect to SELV circuit. Failure to observe this could cause damage to the adapter.

UPS JBUS/MODBUS Adapter User Manual

Chapter 2 Installation 3

Chapter 2 Installation

2.1 Unpacking Inspection

Unpack the adapter, take out the delivery list (see Table 2-1), and check the goods against it. Should there be any discrepancy, contact the distributor immediately.

Table 2-1 Adapter delivery list

S/N. 1 2 Goods Adapter CD Qty. 1 pcs 1 pcs Remark UPS JBUS/MODBUS Adapter User Manual 2.2 Installation Notes

1. The adapter should be installed in the SNMP slot of the UPS or FLP, which is also used for the installation of SNMP card. Therefore, if you use the adapter, you cannot use the SNMP card.

2. The adapter is available in two sizes, please verify that your adapter matches the UPS or FLP (refer to the

hardware description in section 1.3). Otherwise, the adapter cannot be plugged in the SNMP slot of the UPS or FLP. 3. Some electronic components of the adapter are sensitive to static electricity. To prevent static electricity from damaging the adapter, do not touch its electronic components or circuits, also avoid their contact with live objects. Therefore, please hold the side edges of the adapter when moving or installing it.

2.3 Installation Procedures

Please install the adapter in the following sequence: 1. Set the basic parameters of the adapter; 2. Plug the adapter in the SNMP slot; 3. Connect the communication cable;

4. Set the communication parameters in the host software.

2.3.1 Setting Basic Parameters

To enable the functions of the adapter, you must set its basic parameters, which are: ?Physical address ?Communication baud rate

These parameters are set by the 8-bit DIP switch of the adapter (refer to Figure 1-1 for its location). The up position means ON, the down position means OFF, as shown in the following figure.

ON12345678 Figure 2-1 DIP switch

The basic parameters of the adapter are set by Bits 1~7 of the DIP switch, Bit 8 is factory reserved. The setting shown in Figure 2-1 is the factory default.

UPS JBUS/MODBUS Adapter User Manual

4 Chapter 2 Installation

Setting physical address

The physical address of the adapter is set by Bits 1~5. The setting range is 1~31, 0 is factory-reserved setting, 1 is the factory default.

The physical address setting method is shown in Table 2-2:

Table 2-2 Physical address setting method

Physical address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Bit 1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Bit 2 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON Bit 3 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON Bit 4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON Bit 5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ?

Warning

The physical address 0 is factory reserved. You shall not set the physical address to 0; otherwise, the adapter cannot operate normally.

Setting communication baud rate

The communication baud rate of the adapter is set by Bits 6~7, and can be set to 2400bps, 4800bps, 9600bps, or 19200bps. 9600bps is the factory default.

The communication baud rate setting method is shown in Table 2-3:

Table 2-3 Communication baud rate setting method

Communication baud rate (bps) 2400 4800 9600 19200 Bit 6 OFF ON OFF ON Bit 7 OFF OFF ON ON UPS JBUS/MODBUS Adapter User Manual


Libert 485UPS JBUS-MODBUS适配卡用户手册 - 图文(8).doc 将本文的Word文档下载到电脑 下载失败或者文档不完整,请联系客服人员解决!