北京华瑞泰公司 387470481.doc
目
录
第一部分 FWK-F失步解列柜 ................................................................................................. 3 一、概述 ....................................................................................................................................... 3 二、用途与功能 ........................................................................................................................... 4 1 2
UFV-2F型装置主要功能 ..................................................................................................... 4 其他功能 ................................................................................................................................ 4
三、装置输入的模拟量及电气量测量方法 ............................................................................... 5 1 2
装置输入的模拟量 ................................................................................................................ 5 电气量测量方法 .................................................................................................................... 5
四、主要技术参数 ....................................................................................................................... 5 1 2 3 4 5 6 7 8 9 10 11 12 13
额定参数 ................................................................................................................................ 6 过载能力 ................................................................................................................................ 6 整屏功率消耗 ........................................................................................................................ 6 整定范围 ................................................................................................................................ 6 动作时间 ................................................................................................................................ 6 返回系数 ................................................................................................................................ 6 测量精度 ................................................................................................................................ 6 事件记录及数据记录 ............................................................................................................ 7 装置输入量 ............................................................................................................................ 7 装置输出量 ........................................................................................................................ 7 介质强度和绝缘电阻 ........................................................................................................ 8 抗干扰性能 ........................................................................................................................ 8 使用环境条件 .................................................................................................................... 8
第二部分 UFV-2F型失步振荡解列装置 ................................................................................. 9 一、用途及主要功能 ................................................................................................................... 9 二、失步解列的判别方法(工作原理) ............................................................................... 10 1 2 3 4 5
概述 .................................................................................................................................... 10 系统失步振荡过程中相位角的变化规律 ........................................................................ 10 相位角失步振荡判据 ........................................................................................................ 15 保护区范围内的判断及选择性配合 ................................................................................ 17 装置启动判据:相位角启动或功率突变量启动 ............................................................ 18
第 1 页
北京华瑞泰公司 387470481.doc
6 闭锁判据 ........................................................................................................................... 19 7 事故前潮流方向判据 ...................................................................................................... 19 8 9
相位角判据的优点 ............................................................................................................ 20 失步解列判别框图 ............................................................................................................ 20
三、装置的硬件配置 ............................................................................................................... 23 1 2 3 4 5 6
装置的硬件框图 ................................................................................................................ 23 装置的结构及正面布置 .................................................................................................... 23 输出中间板(SZ) ........................................................................................................... 24 出口继电器板(CKZ) ................................................................................................... 26 打印接口板(DYK) ....................................................................................................... 27 装置的背板配线图 ............................................................................................................ 27
四、装置的显示菜单 ............................................................................................................... 28 1 2 3 4
装置的软件结构 ................................................................................................................ 28 主菜单 ................................................................................................................................ 28 当前状态显示菜单 ............................................................................................................ 29 定值设置菜单 .................................................................................................................... 30
5 事件记录显示 ................................................................................................................... 32 6 数据记录显示 ................................................................................................................... 32 7 8 9 10
装置动作后的显示(事故屏幕) .................................................................................... 33 打印选择菜单(召唤打印) ............................................................................................ 33 时钟设置菜单 .................................................................................................................... 34 装置的整组试验菜单 .................................................................................................... 35
11 “关于本装置”菜单 ........................................................................................................ 35 五、防止误动作的闭锁措施(装置的回路自检) ............................................................... 36 第三部分 现场安装调试、运行与维护 ............................................................................... 38 一、现场安装调试 ................................................................................................................... 38 二、现场运行与维护 ............................................................................................................... 39 第四部分 附图:接线原理图.................................................................... 错误!未定义书签。
第 2 页
北京华瑞泰公司 387470481.doc
第一部分
一、概述
线路 FWK-F失步解列柜
旁路
Ⅰ母 Ⅱ母
母联
主变 主变
该装置所适用的厂站系统接线图
当变电站/电厂与主系统失去同步,发生失步振荡时,系统在失步过程中某些地区,尤其是振荡中心附近的电压、频率将大幅度变化,对用电负荷的安全威胁很大,甚至引起大面积停电事故。因此应安装一面FWK-F失步解列柜,要求系统发生振荡事故时解列线路(旁代运行时解列旁路)。
第 3 页
北京华瑞泰公司 387470481.doc 二、用途与功能
1 UFV-2F型装置主要功能
装置的单元处理机1DCJ、2DCJ分别测量线路、旁路的三相电压、三相电流、有功功率和相位角。正常情况下,用线路电气量判失步;投上旁代压板时,装置自动转用旁路电气量判失步。当系统失去同步,发生振荡时,若振荡中心落在预定的动作范围内,装置根据相位角振荡判据,振荡周期次数,有选择地切除联络线本侧或旁路开关,并另输出接点闭锁重合闸。另外预留六对备用出口。 2 其他功能
2.1 UFV-2F装置能自动记录两次事故过程中电压、电流、功率、相位角的变化(事故记录和数据记录),便于事故分析和掌握事故时的动态过程。记录内容在断电后不会消失。 2.2 屏上配一个带汉字库的打印机,事故后自动打印出事故记录和数据记录。 2.3 UFV-2F装置带有RS-485串行通讯口,可将有关信息上送监控系统。
2.4 UFV-2F装置具有GPS脉冲自动对时功能,可保证时钟回路计时准确,避免累计误差。 2.5 采用3U0、3I0、失压等多种闭锁措施,以防止由于短路故障、PT断线、CT断线或电压异常情况可能引起的误动作,并发中央告警信号。
2.6 具有完善的自检措施及整组自试功能,使现场运行维护更为简单、方便。正常运行自检发现异常后会闭锁出口并发中央告警信号,保证了装置的安全性。
2.7 主机板上具有滤除高次谐波的二阶带通滤波器,可有效防止冲击负荷、电气化铁路等谐波源的影响。
2.8 装置的电压电流定值、功率定值及时间定值均连续可调。此外,定值显示及设定修改方便、准确、直观,定值存放在E2PROM内,断电后定值不会消失。面板上设有定值允许设置开关,只有该开关拨在“允许”位置时才能写进新的定值;定值设置开关在“允许”位置时,装置不进行事故判断,定值修改完毕后必须及时将该开关拨回“禁止”位置;并且仅在设置开关拨回“禁止”位置时方可返回主菜单。
2.9 装置面板上的信号灯可准确反映出装置的运行、启动、动作、异常等情况。
2.10通过装置面板上的9个按键,可以选择各种显示菜单、修改整定值、设定日期时间、召唤打印、结束打印、进行整组检查试验及动作信号的复归。
2.11 通过装置面板上的液晶显示屏以菜单方式显示时间、正常运行测量值、整定值、事件记录及数据记录等。自检发现异常或装置动作后,均会立即发出中央告警信号,并在当前显示菜单屏幕上显示异常的内容,或自动停止显示当前菜单,改为显示动作的内容。UFV-2F装置采用汉字显示方式。
第 4 页
北京华瑞泰公司 387470481.doc 三、装置输入的模拟量及电气量测量方法
1 装置输入的模拟量
UFV-2F型装置测量线路的三相电压(UA、UB、UC、UN)、三相电流(IA、IB、IC、IN)、旁路的三相电压(PUA、PUB、PUC、PUN)、三相电流(PIA、PIB、PIC、PIN)、有功功率和相位角。
直流电源通过屏后抗干扰端子后,再引入装置。抗干扰端子内部装有一个电容(C=0.1μf,耐压3kV),用以滤去高频干扰,防止电压、电流回路的干扰电压侵入微机装置内部。
交直流电压通过空气开关1ZK~3ZK再和装置相连。ZK是具有高分断能力的空气开关,具有过流反时限脱扣性能和短路瞬时脱扣性能,用以防止短路事故损坏装置、外部PT或直流电源设备。 2 电气量测量方法
2.1 电压、电流、功率的测量方法
装置的微机部分对输入的交流电压UA、UB、UC及交流电流IA、IB、IC的瞬时值进行采样,采样周期为1.667ms(20ms采样12点),然后按以下算法计算出电压、电流有效值、有功功率值。
UAK=3U0=
1122?u12k?1AK
kV kV
1122?(uAK?uBK?uCK)12k?1(相当3U0=UA+UB+UC) IAK=3I0=
1122?i12k?1AK112?(12k?1
A A
2iAK?iBK?iCK)
(相当3I0=IA+IB+IC)
112P=?(uAiA?uBiB?uCiC)K
12k?1 MW
(三相对称时,P=3UAKIAKCosφ)
2.2 相位角φ的测量方法
2F装置相位角的测量方法:先计算出有功功率P及无功Q,再用以下公式求出φ。这一测量方法具有良好的连续性及抗扰动性。
相位角φ:tgφ = Q / P
四、主要技术参数