兰州交通大学毕业设计(论文)
目录
第一章 原始资料 ....................................................................1 第二章 石家庄市室外气象资料及室内参数的确定 .........................................1 第三章 夏季空调冷负荷计算 ..........................................................2 第四章 空调处理方案选择 ............................................................6
4.1 空气处理方案的确定 .........................................................6 4.2 气流组织设计 ...............................................................9 第五章 空气处理过程的计算 .........................................................12
5.1 计算方法及步骤 ............................................................12 5.2 风机盘管加新风系统空气处理过程 .............................................13 第六章 系统设备选型 ...............................................................15
6.1 风机盘管的选择 ............................................................15 6.2 新风机组的选择 ............................................................15 第七章 水力计算 ...................................................................16
7.1 风管水力计算 ..............................................................16 7.2 水管水力计算 ..............................................................17 第八章 设备选择 ...................................................................18 第九章 防火、防排烟及排风系统的选择与布置 ..........................................26 第十章 空调系统的减震和防噪 .......................................................28
10.1 风机设备减震计算 .........................................................28 10.2 噪声控制计算 .............................................................29 第十一章 空调系统的节能与运行工况调节 ..............................................30
11.1 系统的节能 ...............................................................30 11.2 系统的运行工况调节 ......................................................30
-
兰州交通大学毕业设计(论文)
摘要
本工程为石家庄市某图书馆空调工程,总高27.3米。建筑主体外墙结构采用厚
度为300mm的加气混凝土砌块,屋顶采用钢筋混凝土板,保温层采用沥青膨胀珍珠岩,厚度200mm。地下一层,地上六层,一层为休息展厅、自习室及其服务设施用房;二层为中庭、阅览室及报告厅、会议室、资料室;三层为文学和社会科学借阅厅、网络中心;四层为工科、计算机、外文图书借阅厅和数,理,农,生图书借阅厅;五层为工具书检索厅、文献资料中心、综合展厅、艺术作品观摩室、教师图书借阅厅及研究室;六层为学者文库、要籍厅、样本图书查阅厅。地下室为六级人防工事,平时为戊类仓库,总建筑面积26515.2平方米,建筑夏季总冷负荷季为1454KW。
根据本建筑房间结构形式的特点,本工程的空调系统选用风机盘管加新风系统.每层设有新风机组,可以由同层的新风机组送入室内,和风机盘管一起满足室内的冷负荷。其次,本设计水系统采用两管制、闭式、一次泵定流量系统,各层水管同程布置。两管制系统采用同一套供回水管路,夏季供冷水。两管制系统具有管理方便,一次性投资小等优点。在本设计中同层的水平管和立管上皆采用同程系统,这样有利于管路阻力的平衡也能够给施工带来方便而减少工程造价。 关键词:空调工程,风机盘管,冷负荷,水系统
-
兰州交通大学毕业设计(论文)
ABSTRACT
This works for air conditioning engineering in a library of Shijiazhuang City, a total of 27.3 meters high. The main building exterior wall structure with the thickness of aerated concrete block 300mm, the roof is made of reinforced concrete plate, insulation layer using asphalt expanded perlite, thickness 200mm. Underground layer, the ground layer six, a layer for the rest room,study room and facilities for housing; the two layer is the atrium, reading roomand hall, conference room, reference room; the three layer is the literary and social scientific reading hall, network center; the four layer is the engineering,computer, foreign language books reading room and the number of students,science, agriculture, library hall; the five layer is the reference book Hall,documentation centre, comprehensive exhibition hall, art viewing room hall andstudy of teachers' books reading room, library, scholars; the six layer is to takeoffice, sample book consulting department. The basement is six grade civil air defence fortifications, usually for class E warehouse, a total construction area of 26515.2 square meters, building in summer season total cooling load is 1454KW.
According to the characteristics of the room structure form of this building, air conditioning system of this project selection of fan coil unit plus fresh airsystem. Each layer is provided with a fresh air unit, by the same air units layerinto the interior, and a fan coil to meet the indoor cooling load. Secondly, thedesign of water system adopts two control, closed, a constant flow pump system, each layer of pipe layout with the distance. Two control system usingthe same set of supply and return water pipes, summer cooling. Two controlsystem has the advantages of small investment and convenient management,etc.. In the design of the same layer horizontal pipe and vertical pipe are the same way system, which is conducive to the pipeline resistance balance alsocan bring convenience to the construction and reduce the project cost.
Keywords: air conditioning, fan coil, cooling load, water system
-
兰州交通大学毕业设计(论文)
第一章 原始资料
1.1地理位置:河北省石家庄市。 1.2 建筑概况
该建筑类型为公共建筑,总建筑面积26515.2㎡。该建筑主体地上六层,一层为休息展厅、自习室及其服务设施用房;二层为中庭、阅览室及报告厅、会议室、资料室;三层为文学和社会科学借阅厅、网络中心;四层为工科、计算机、外文图书借阅厅和数,理,农,生图书借阅厅;五层为工具书检索厅、文献资料中心、综合展厅、艺术作品观摩室、教师图书借阅厅及研究室;六层为学者文库、要籍厅、样本图书查阅厅。地下室为六级人防工事,平时为戊类仓库。
1.3层高:首层高度4.8m,二~六层高度4.5m,地下室高度3.9m。 1.4围护结构:
㈠墙体结构
外墙结构采用300厚加气混凝土砌块,传热系数为K=0.59W/㎡?℃;内墙为200后加气混凝土砌块,传热系数为K=0.86W/㎡?℃。 ㈡门窗
⑴外窗:铝合金高强度气密中空玻璃窗(K=2.99W/m2.℃); 玻璃幕墙(K=2.4 W/m2.℃),每个窗户开启扇均做纱窗,不设外遮阳。 ⑵外门:玻璃门(K=5.7 W/m2.℃) ⑶内门:木门。
1.5系统:全楼采用风机盘管加新风空调系统,全年负荷全部由空调系统供给。
第二章 石家庄市室外气象资料及室内参数的确定
2.1地理位置: 河北省石家庄市
北纬38o02′
东经114o25′
2.2 夏季参数
-
1
兰州交通大学毕业设计(论文)
由新规范《GB50736-2012》气象参数查得石家庄市夏季室外气象参数如下:
大气压:99.58 kPa 室外计算干球温度: 35.1℃ 室外计算湿球温度26.8℃ 夏季日平均干球温度: 30.0℃ 室外平均风速: 1.7 m/s
2.3 冬季参数
由新规范《GB50736-2012》气象参数查得石家庄市冬季室外气象参数如下:
大气压:101.72kPa
室外计算干球温度:-8.80 ℃ 室外相对湿度:55 %
室外平均风速1.8 m/s
2.4 空调室内设计参数
表2-1
房间 门厅 自习室 会议室 休息厅 阅览室 展览厅 讨论室 管理室 研究室 -
夏季设计温度 25℃ 25℃ 25℃ 25℃ 25℃ 25℃ 25℃ 25℃ 25℃ 2
夏季设计湿度 60% 60% 60% 60% 60% 60% 60% 60% 60%