3.13.4.4 Output Buffer, Communication Block from PLC to PFEA 112 输出缓冲器,从PLC到PFEA 112的通讯

This section specifies Boolean values in the output buffer communication block. 这节指定在输出缓冲器通讯块的逻辑值。

3.14 Commissioning of Optional units 可选单元的试运转 3.14.1 Insulation Amplifier PXUB 201 隔离放大器PXUB 201

The insulation amplifier is connected to the tension electronics voltage output. 隔离放大器和张力传感器电压输出连接。 S1 is normally set for voltage 1:1 ratio. S1是电压比率1:1的通常设置。

The output is selected to generate a voltage or current output by means of switch S1 and S2. 这输出是由开关S1和S2选择来产生的一个电压或电流输出。 Shower response is selected by means of switch S2, position 3. 大量响应由开关S2在位置3进行挑选。 The switches are located inside the unit. 开关在单元内部安装。

You must open the insulation amplifier to be able to set the switches S1 and S2. 你必须打开隔离放大器才可以设置开关S1和S2。 1. Demount the insulation amplifier from the DIN rail. 从DIN铁轨卸下隔离放大器。

Use a screw drive to unload the spring at the bottom of the insulation amplifier. 用螺丝刀拨底部的弹簧卸下隔离放大器。

2. Press down the snap-locks on both sides of the insulation amplifier.

按下在隔离放大器两端的弹簧锁。

3. Pull the top lid open, until you see both the switches S1 and S2.

拉开顶部的盖子,直到可以看到S1和S2两个开关。 4. Set the switches S1 and S2.

设置S1和S2。

5. Slide back the top lid to locked position.

将顶盖放到锁定位置。

6. Remount the insulation amplifier on the DIN rail.

在DIN铁轨重装绝缘放大器。

Chapter 4 Operation 第四章 操作

4.1 About this chapter 关于本章节

Your measurement system does not need any attention during normal operation. Measurement runs continuously as long as the system is switched on. However, you need to know how to start and shut down the system, see Section 4.4 Start-up and shut-down.

正常工作时测量系统将不需要关注。系统运行多久测量装置也运行多久。你应该知道怎样开始和关闭系统,参阅4.4章节开始和关闭。 4.2 Safety instructions安全教育(说明)

Read and follow the safety instructions given in Chapter 1 Introduction, before starting any

21

operation work. However, local statutory regulations, if stricter, are to take precedence.

在开始任何操作前,阅读并遵循第一章提供的安全说明。如果当地法规严格,请优先。 4.3 operating devices操作装置

The LED-indication and operator keys are described in Figure 4-1.

液晶指示和操作键盘在4-1中叙述。 4.4 Start-up and shut-down启动和关闭 4.4.1 Start-up 启动

The tension electronics is started and shut down using an external ON/OFF switch (not supplied by ABB). During normal service no action from the operator is required.

张力传感器开始和结束由外部ON/OFF开关(不由ABB提供)控制。正常维修时不应该有任何操作。

1. Check that the main tension control machinery is ready for normal run.

检查主张力控制机构已经可以正常运转。

2. Switch on the tension electronics by setting the external ON/OFF switch to position ON. For the

IP 65-version (NEMA 4) also set the internal switch to “ON”.

将外部ON/OFF开关置于ON以接通张力传感器。对于IP 65-version (NEMA 4)将内部开关置于ON。 3. Check that:

检查

- the display is illuminated - 显示正常

- the “Power” indicator is lit - 电源正常

- the “Status” indicator is lit (green light). Red light indicates an error. - 状态正常(绿灯)。红灯显示错误。 4.4.2 Shut-down关闭

Shut-down the tension electronics by setting the external ON/OFF switch to position OFF. 关闭张力传感器只要将外部ON/OFF转换到OFF位置。 4.5 Normal Run正常运转

The measurement equipment should be permanently on to achieve best measuring result. This allows the load cells and electronics to operate under even temperature conditions. The measuring equipment is designed for continuous duty.

测量装置应该是稳定的以得到最好的测量结果。这允许测压单元和传感器工作在温度条件下。测量装置应该设计为连续工作。 4.6 Operator Menus操作菜单

This section describes the operator menus. The updating time for displayed values is 500ms. Use UP and DOWN to switch between menus.

着部分说明操作菜单。显示的更新时间是500ms.用UP和DOWN切换菜单。 Web tension value幅面张力值 Tension A value张力A值 Tension B value张力B值

Tension diff A-B Value张力差A-B值

Error and warning messages错误和警告信息 4.6.1 web tension张力

22

4.6.1.1 Standard Roll (two load cells)标准辊(两个测压单元)

The following menus are available when a standard roll (two load cells) is connected to the tension electronics:

当标准辊(双测压单元)连接到张力传感器,以下的菜单是可用的。 ? Web Tension纸幅张力

Shows the total web tension measured by load cell A and load cell B 显示由测压单元A和B测量的总的幅面张力。 ? Tension A张力A

Shows the part of web tension measured by load cell A 显示测压单元A测量的部分幅面张力。 ? Tension B张力B

Shows the part of web tension measured by load cell B] 显示测压单元B测量的部分幅面张力。 ? Tension Diff A-B 张力差A-B

Shows the difference between Tension A and Tension B 显示张力A和B的不同。

4.6.1.2 Single Side Measurement (one load cell)仅一边测量(一个测压单元)

The following menu is shown when only one load cell (single side measurement) is connected to the tension electronics:

下面的菜单显示的是一个测压单元(单边测量)用在张力传感器: ? Web Tension 幅面张力

Web Tension is displayed for single side measurement (only load cell A connected). 幅面张力由单边测量(仅测压单元A)显示。

Web Tension is the tension measured by load cell A multiplied by 2. 幅面张力由2倍测压单元A测量。

4.6.2 Error and Warning Messages出错和警告信息

An ERROR is something that causes the tension electronics to function incorrectly. 错误是导致张力传感器不正常运行的原因。

A WARNING is something that might affect the accuracy of the measurement. 警告是可能影响测量精度的原因。

When a warning or an error occurs, a warning or an error message is displayed on the Operator Panel and the “Status” indication turns from green to red.

当警告和错误出现,相应信息将出现在操作面板同时“状态“将由绿转红。 When RIGHT is pressed the message disappears from the display. 当RIGHT按下信息将从面板消失。

If the problem that activated the warning or error message has disappeared the “Status” indication turns to green.

如果引起警告和错误信息的问题已经消失“状态“将变绿。

If the error or warning remains the “Status” indication is red. Use the DOWN to step to the last menu, where you can read the error or warning message.

如果错误或警告仍然指示的是红。退到主菜单,就可以看到错误和警告信息。 For handling Error and Warning messages see Chapter 6 Fault-tracing. 处理错误和警告信息请参阅第6章。

23

Chapter 5 Maintenance 第5章 维护

5.1 About this Chapter 关于此章节

Under normal operating conditions, your system does not require any maintenance. However, we recommend you to perform regular checks. The following preventive measures may be taken depending on the type of environment in which your system operates.

在一般工作条件下,您的系统不需要任何维护。但我们推荐您定期的进行检查。下列预防措施可以在系统运行的环境下实施。 5.2 Preventive Maintenance 定期检修

Unit 单位 Measures 方法

Load cells Protect the load cells from prolonged contact with corrosive elements. 测压单元 Check the fixing screws and re-tighten if necessary.

Check the gaps between load cell and adapter plates to ensure that they are not clogged

with dirt, which can cause a shunt force into the load cell.

Clean the gaps with compressed air if necessary.

让测压单元远离腐蚀性物质。检查紧固螺丝。检查测压单元和适配器间隙是否有

灰尘,如果必要用压缩空气清理。

Tension Electronics Check that the circuit boards are properly secured and that cables or wires are

not damaged.

Check that all terminal screws and cable glands are properly tightened.

检查电路板绝对安全电缆没有受到损坏。检查所有接线螺丝电缆密封管适当的拉

紧。

Connection cables Check that the connection cables between the load cells and the tension

electronics are not damaged.

确保测压单元和张力传感器之间的电缆没有被损坏。

Chapter 6 Fault-tracing 故障追踪

6.1 About this Chapter 关于此章

During the working life of your measurement system, events may occur that disturb it and your process. These disturbances may appear in many different ways and the reason for the fault can be difficult to find. However, disturbances similar in character can be grouped together and usually they have the same or similar sources of error.

在测量系统工作期间,需要处理许多干扰装置的问题。这些干扰是多渠道的,很难被发现。把类似的干扰归纳在一起,(会发现)通常是相同的或类似的干扰源。

The fault-tracing instructions in this chapter will help you to quickly find and correct the most common faults.

本章所阐述的故障追踪可以很快的发现和解决大部分的相同错误。 6.2 Safety Instructions 安全说明

Read and follow the safety instructions given in Chapter 1 Introduction when tracing faults. However, local statutory regulations, if stricter, are to take precedence.

故障错误时,请阅读和按照第一章的安全说明。但如果当地法规更严格,请优先。 6.3 Interchangeability 可交换性

Unit 单元 Measures方法

Tension Electronics The tension electronics PFEA 111/112 is interchangeable with a

24

张力传感器 tension electronics of the same type. A new setup is required.

PFEA 111/112张力传感器和同型号之间是可互换的。这需要重起。 Load cells The load cells are directly interchangeable with other load cells 测压单元 of the same type.

Zero setting PFEA 111/112 and resetting “Maximum Load A” or “Maximum Load B” are required after a load cell has been replaced.

测压单元可直接同其他同型号的互换。PFEA111/112的零点设置和重新设置A

的最大量或B的最大量要求在一个测压单元已经被替换后。

6.4 Necessary Equipment and Documentation 必要的设备和文件 The following items are required to perform fault-tracing and repairs: 要完成故障追踪和修理要按照以下条款:

? Cable diagrams, see Appendix (B,C,D or E for) for installed load cell type图表,参照附件 ? Service tools维修工具 ? Torque wrench 转矩扳手 ? Multimeter 万用表

6.5 Fault-tracing Procedure错误追踪程序

Fault in the故障源 Fault symptoms故障征兆

Mechanical installation Faults in the mechanical installation usually manifest themselves as 机械装置 an unstable zero point or incorrect sensitivity.

If a fault is associated with a process parameter, such as the temperature, or can be

linked with a particular operation, the fault is likely to emanate from the mechanical part of the installation.

机械装置的故障一般表现为自身零点不稳定或错误的灵敏度。 如果故障和过程参数有关,如温度,或和特殊的操作联系起来,故障有可能是自身部件引起的。

Load cells Calibration data for a load cell do not change gradually. A load cell,

测压单元 depending on its size and type, can withstand up to five times the nominal load

in the measuring direction. An event in the process line, such as web breakage, may cause an overloading large enough to alter load cell data. Depending on the amount of overload, it may be sufficient to zero set.

压头的标定参数不会因时间而改变,一个压头,可以直接测量其5倍的正常负荷,这由其尺寸和型号所决定的。生产线的事故例如断带会使压头有足够大的过载,零位的调整取决于过载量。

Cabling Problems such as malfunctions or unstable zero point may arise 卷取辊

from faulty cables or wiring.

当出现故障或零点漂移可能是电缆引起的。

Proximity to noisy cables may cause interference problems. 附近如有带噪声的电缆可能引起干扰问题。

Incorrect installation, such as cable cores connected asymmetrically

or screens earthed at both ends instead or only at one end, may show up as an unstable zero point。 电缆连接不良、两端屏蔽接地代替了一端接地的,类似这种安装可能会引起零点漂移。

25