煤矿井下供电系统整定值11.3(2)

2019-05-26 18:16

3、矿用干式变压器的电阻、电抗值 型号 KBSG-200/6 KBSG-315/6

1)、中央变电所低压侧:KBSG—315/6 查表得: Rb=0.0106Ω Xb=0.06Ω Xx=0.0288Ω Kb=8.7 YJV22-3×70高压电缆 R1=0.294Ω X1=0.072Ω L=700M 式中:Rb 为变压器电阻,Xb为变压器电抗,Xx为系统电抗,Kb 为变压器变比。

变压器二次出口端的短路电流Id中计算: Id=Ue/2√∑R+∑X

∑R=0.294×0.7÷8.7+0.0106=0.01332Ω ∑X=0.0288+0.072×0.7÷8.72+0.06=0.0894Ω Id=690/2√∑R2+∑X2=690/2×0.09 =3833.3A

1、暗主井绞车电机短路电流:

L=50M(70mm2 R=0.315 X=0.078) R2=0.315×0.05=0.015Ω X2=0.078×0.05=0.004Ω ∑R=0.015+0.01332=0.028Ω

2

2

2

电阻(Ω) 0.0168 0.0106 电抗(Ω) 0.0946 0.06

∑X=0.004+0.0894=0.093Ω Z0=√∑R2+∑X2=0.09Ω Id1=690/2×0.09=3833 A

2、228绞车电机短路电流: L=320M(25mm2-320M) R2=0.864×0.32=0.27Ω X2=0.088×0.32=0.028Ω ∑R=0.27+0.01332=0.28Ω ∑X=0.028+0.0894=0.117Ω Z0=√∑R2+∑X2=0.3Ω Id1=690/2×0.3=1150 A

3、样板队喷浆机短路电流: L=160M (16mm2-160M) R2=1.37×0.16=0.219Ω X2=0.09×0.16=0.014Ω ∑R=0.219+0.01332=0.23Ω ∑X=0.014+0.0894=0.1Ω Z0=√∑R2+∑X2=0.25Ω Id2=690/2×0.25=1380 A

(2)(2)(2)

二、中央变电所过流整定计算:

1、总开关KBZ9-400及试验开关KBZ9-400,分开关整定值: Idz=(4×2+132+7.5×3+40+5.5)×1.15

=239A

过流插件整定为:过载整定Iz≤239/400=0.59,旋钮位置0.6 短路整定:短路保护执行继电器IZ =8Ie=8×239=1912A 即:1912/400=4.8 旋钮位置5位置即可 2、分开关KBZ9-200整定值: Idz=(40+5.5)×1.15

=52A

过流插件整定为:过载整定Iz≤52/200=0.26,旋钮位置0.3 短路整定:短路保护执行继电器IZ =8Ie=8×52=416A 即:416/200=2.08 旋钮位置2位置即可 灵敏度校验: Id2(2)/ Idz=1150/416=2.7>1.5 合格 3、暗主井DW80-350整定值:

Idz≥IDq=6×132×1.15+7.5×2×1.15+4×2×1.15=937.25

整定:1000A

灵敏度校验: Id2(2)/ Idz=3833/1000=3.8>1.5 合格

2)、118采区变电所 动力变压器KSBG-200/6 查表得 Rb=0.0168Ω Xb=0.0946Ω Xx=0.0288Ω Kb=8.7 高压电缆 50mm R1=0.412Ω X1=0.075Ω L=680M

2

动力变压器二次出口端的短路电流Id计算: Id=Ue/2√∑R2+∑X2

∑R=0.412×0.68÷8.7+0.0168=0.02Ω

∑X=0.0288+0.075×0.68÷8.7+0.0946=0.124Ω Id=690/2√∑R+∑X=690/2×0.125 =2760 A

1、218辅助上山绞车房馈电开关处短路电流: L=510M ( 25mm2-510M) R2=0.864×0.51=0.44Ω X2=0.088×0.51=0.045Ω ∑R=0.44+0.02=0.46Ω ∑X=0.045+0.124=0.169Ω Z0=√∑R2+∑X2=0.49Ω Id2(2)=690/2×0.49=704 A

2、218-220馈电开关处短路电流: L=310M ( 25mm2-310M ) R2=0.864×0.31=0.268Ω X2=0.088×0.31=0.027Ω ∑R=0.268+0.02=0.288Ω ∑X=0.027+0.124=0.151Ω

2

2

2

2

Z0=√∑R2+∑X2=0.32Ω Id2(2)=690/2×0.32=1078 A

3、218绞车房电机处短路电流: L=90M ( 25mm-90M ) R2=0.864×0.09=0.077Ω X2=0.088×0.09=0.007Ω ∑R=0.077+0.02=0.097Ω ∑X=0.007+0.124=0.131Ω Z0=√∑R2+∑X2=0.16Ω Id2(2)=690/2×0.16=2156 A

4、218-220掘五队回柱绞车处短路电流: L=170M (16mm2-110M 25mm2-60M) R2=1.37×0.11+0.864×0.06=0.2Ω X2=0.09×0.11+0.088×0.06=0.014Ω ∑R=0.2+0.02=0.22Ω ∑X=0.014+0.124=0.138Ω Z0=√∑R2+∑X2=0.25Ω Id2(2)=690/2×0.25=1380 A

5、218-220楚二队喷浆机处短路电流:

2