L=140M (16mm2-80M 25mm2-60M) R2=1.37×0.08+0.864×0.06=0.16Ω X2=0.09×0.08+0.088×0.06=0.012Ω ∑R=0.16+0.02=0.18Ω ∑X=0.012+0.124=0.136Ω Z0=√∑R2+∑X2=0.22Ω Id2(2)=690/2×0.22=1568 A
6、218-261馈电开关处短路电流: L=820M (50mm2-820M) R2=0.448×0.82=0.7Ω X2=0.081×0.82=0.072Ω ∑R=0.7+0.02=0.72Ω ∑X=0.072+0.124=0.196Ω Z0=√∑R2+∑X2=0.74Ω Id2(2)=690/2×0.74=466 A
7、218-261掘一队回柱绞车电机处短路电流: L=240M ( 25mm2-130M 16mm2-110M ) R2=0.864×0.13+1.37×0.11=0.26Ω X2=0.088×0.13+0.09×0.11=0.02Ω ∑R=0.26+0.02=0.28Ω
∑X=0.02+0.124=0.144Ω Z0=√∑R2+∑X2=0.3Ω Id2=690/2×0.3=1150 A
8、218-300馈电开关处短路电流: L=460M ( 50mm2-460M ) R2=0.448×0.46=0.206Ω X2=0.081×0.46=0.037Ω ∑R=0.206+0.02=0.226Ω ∑X=0.037+0.124=0.161Ω Z0=√∑R2+∑X2=0.27Ω Id2=690/2×0.27=1278 A
9、218辅助上山馈电开关处短路电流: L=630M ( 50mm2-630M ) R2=0.448×0.63=0.28Ω X2=0.081×0.63=0.05Ω ∑R=0.28+0.02=0.3Ω ∑X=0.05+0.124=0.174Ω Z0=√∑R2+∑X2=0.34Ω Id2=690/2×0.34=1015 A
(2)(2)(2)
10、218-300掘四队喷浆机处短路电流: L=150M ( 16mm2-150M ) R2=1.37×0.15=0.21Ω X2=0.09×0.15=0.014Ω ∑R=0.21+0.02=0.23Ω ∑X=0.014+0.124=0.14Ω Z0=√∑R2+∑X2=0.27Ω Id2(2)=690/2×0.27=1278 A
二、118变电所过流整定:
1、118变电所高压开关(BGP9L-6G高爆开关)整定: 高压开关电流互感器为:50/5。 变压器(KBSG200/5)额定电流为:25.4A
根据该配电装置微机高压综合保护器说明书要求:过载电流整定为25A,旋钮位置调到:0.5档,短路整定为400A(一 般整定为额定电流的8-10),旋钮位置调到:8.0档
2、变电所KBZ9-400/660总开关及试验开关的整定值: Idz总=(45×2+40+7.5×2+5.5×5+1.7×2+17)×1.15=222 A. 过流插件整定为:过载整定Iz=222/400=0.55,旋钮位置0.6 短路整定: 短路保护执行继电器IZ =8Ie=8×222=1776 A 即:1776/400=4.4旋钮位置5
3、送238分开关KBZ9-200/660整定值: Idz=(40+5.5×3+7.5+1.7)×1.15 =75A
过流插件整定为:过载整定Iz=75/200=0.37,旋钮位置0.4 短路整定: 短路保护执行继电器IZ =8Ie=8×75=600A 即:600/200=3旋钮位置3
4、238绞车房KBZ9-200/660馈电开关整定值: Idz=40×1.15 =46 A
过流插件整定为:过载整定Iz≤46/200=0.23,旋钮位置0.3 短路整定: 短路保护执行继电器IZ =8Ie=8×46=368 A 即:368/200=1.8旋钮位置2 校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 704/368=1.9>1.5 满足灵敏度要求
5、218-220 KBZ9-200/660馈电开关整定值: Idz=(5.5×3+7.5+1.7)×1.15 =29 A
过流插件整定为:过载整定Iz≤29/200=0.14,旋钮位置0.2
短路整定: 短路保护执行继电器IZ =8Ie=8×29=232A 即:232/200=1.16旋钮位置1 校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 466/216=2.1>1.5 满足灵敏度要求
6、送218轨道下山KBZ9-200/660整定值:
Idz=(45×2+5.5×2+7.5+1.7+17)×1.15 =146 A
过流插件整定为:过载整定Iz≤146/200=0.73,旋钮位置0.8 短路整定: 短路保护执行继电器IZ =8Ie=8×146=1168 A 即:1168/200=5.8旋钮位置6
7、218-261 KBZ9-200/660馈电开关整定值: Idz=(5.5+7.5+1.7)×1.15 =17 A
过流插件整定为:过载整定Iz≤17/200=0.08,旋钮位置0.1 短路整定: 短路保护执行继电器IZ =8Ie=8×17=136 A 即:136/200=0.68旋钮位置1 校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 1150/136=8.4>1.5 满足灵敏度要求