4、268-220 三专馈电开关KBZ9-200/660整定值: Idz=(11×2)×1.15 =25 A
过流插件整定为:过载整定Iz≤25/200=0.12,旋钮位置0.2 短路整定: 短路保护执行继电器IZ =8Ie=8×25=200 A 即:200/200=1旋钮位置1 校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 1150/200=5.7>1.5 满足灵敏度要求
5、268-261 三专馈电开关KBZ9-200/660整定值: Idz=11×1.15 =12 A
过流插件整定为:过载整定Iz≤12/200=0.06,旋钮位置0.1 短路整定: 短路保护执行继电器IZ =8Ie=8×12=96 A 即:96/200=0.48旋钮位置1 校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 885/96=9.2>1.5 满足灵敏度要求
4)-300中央变电所 KSBG-315/6 查表得 Rb=0.0106Ω Xb=0.06Ω Xx=0.0288Ω Kb=8.7
高压电缆70mm2 R1=0.294Ω X1=0.072Ω L=800M
1、变压器二次出口端的短路电流Id北计算: Id=Ue/2√∑R+∑X
∑R=0.294×0.8÷8.7+0.0106=0.014Ω ∑X=0.0288+0.072×0.8÷8.72+0.066=0.096Ω Id =690/2√∑R2+∑X2=690/2×0.099=3484.8(A)
二、-300变电所过流整定:
-300变电所未供电,未进行整定计算。
5)、248 -300采区变电所: KSBG—315/6 查表得: Rb=0.0106Ω Xb=0.06Ω Xx=0.0288Ω Kb=8.7 YJV22-3×25高压电缆R1=0.824Ω X1=0.085Ω L=460M 变压器二次出口端的短路电流Id中计算: Id=Ue/2√∑R2+∑X2
∑R=0.824×0.46÷8.72+0.0106=0.016Ω ∑X=0.0288+0.46×0.085÷8.72+0.066=0.095Ω Id =690/2√∑R2+∑X2=690/2×0.096 =3594A
1、248 -300主石门馈电开关处短路电流: L=150M ( 35mm-150M )
22
2
2
R2=0.616×0.15=0.092Ω X2=0.084×0.15=0.012Ω ∑R=0.012+0.016=0.028Ω ∑X=0.032+0.095=0.127Ω Z0=√∑R+∑X=0.13Ω Id2(2)=690/2×0.13=2654 A
2、采八队回柱绞车处短路电流: L=240M (25mm2-180M 16mm2-60M) R2=0.864×0.18+1.37×0.06=0.23Ω X2=0.088×0.18+0.09×0.06=0.021Ω ∑R=0.23+0.016=0.246Ω ∑X=0.021+0.095=0.116Ω Z0=√∑R2+∑X2=0.27Ω Id2(2)=690/2×0.27=1277 A
3、248-300石门馈电开关处短路电流: L=390M (35mm2-150M+25mm2-240M ) R2=0.864×0.24+0.616×0.15=0.299Ω X2=0.088×0.24+0.084×0.15=0.033Ω ∑R=0.299+0.016=0.315Ω ∑X=0.033+0.095=0.128Ω
2
2
Z0=√∑R2+∑X2=0.34Ω Id2(2)=690/2×0.34=1014 A
4、2486掘六队电煤钻处短路电流: L=140M ( 16mm-140M ) R2=1.37×0.14=0.19Ω X2=0.09×0.14=0.013Ω ∑R=0.19+0.0242=0.21Ω ∑X=0.013+0.124=0.137Ω Z0=√∑R2+∑X2=0.25Ω Id2(2)=690/2×0.25=1380 A
5、2685掘八队回柱绞车处短路电流: L=150M ( 16mm2-150M ) R2=1.37×0.15=0.21Ω X2=0.09×0.15=0.014Ω ∑R=0.21+0.016=0.226Ω ∑X=0.014+0.095=0.109Ω Z0=√∑R2+∑X2=0.251Ω Id2(2)=690/2×0.251=1374 A
2
二、248 -300变电所过流整定:
1、总开关KBZ9-400及试验开关KBZ9-400开关整定值: Idz=(7.5×3+5.5×6+1.7×3)×1.15 =72 A
过流插件整定为:过载整定Iz≤72/400=0.18,旋钮位置0.2 短路整定: 短路保护执行继电器IZ =8Ie=8×72=576 A 即:576/400=1.44旋钮位置2
2、送-300北大巷分开关KBZ9-200开关整定值: Idz=(7.5×4+5.5×5+1.7×3)×1.15 =72 A
过流插件整定为:过载整定Iz≤72/200=0.36,旋钮位置0.4 短路整定: 短路保护执行继电器IZ =8Ie=8×72=576 A 即:576/200=2.88旋钮位置3
校验灵敏度:
最远处的短路电流和短路保护执行继电器电流之比即: 1014/576=1.8>1.5 满足灵敏度要求
3、248-300主石门馈电开关KBZ9-200/660整定值: Idz=(5.5+7.5+1.7)×1.15 =17 A
过流插件整定为:过载整定Iz≤17/200=0.08,旋钮位置0.1