查附录三表5得,R1=0.315Ω X1=0.078Ω
Rz1=0.315×0.65= 0.20475Ω
Xz1=0.078×0.65= 0.0507Ω ∑R=0.0171944+0.20475=0.2219Ω ∑X=0.15349+0.0507=0.20419Ω
Id2=Ue/2((∑R2+∑X2))0.5=1200/2(0.22192+0.204192)0.5=1990A (3)工作面供电系统图中综掘机前两相短路电流Id3的计算
已知变压器二次电压为1200V,容量为630kVA,MYP-3×70+1×35mm2电缆长度为200m
MYP-3×70+1×35mm2电缆的电阻、电抗: 查附录三表5得,R1=0.315Ω X1=0.078Ω
Rz1=0.315×0.2=0.063Ω
Xz1=0.078×0.2=0.0156Ω ∑R=0.2219+0.063=0.2849Ω ∑X=0.20419+0.0156=0.21979Ω
Id3=Ue/2(∑R2+∑X2)0.5=1200/2(0.28492+0.219792)0.5=1667A (4)工作面供电系统图中涨紧绞车电机前两相短路电流Id4的计算
已知变压器二次电压为1200V,容量为630kVA,MYP-3×6+1×3mm2电缆长度为50m
MYP-3×6+1×3mm2电缆的电阻、电抗: 查附录三表5得,R1=3.69Ω X1=0.095Ω
Rz1=3.69×0.05=0.1845Ω
Xz1=0.095×0.05=0.00475Ω ∑R=0.2219+0.1845=0.4064Ω ∑X=0.20419+0.00475=0.20894Ω Id4=Ue/2(∑R2+∑X2)0.5=1200/2(0.40642+0.208942)0.5=1313A (5)工作面供电系统图中潜水泵前两相短路电流Id5的计算
已知变压器二次电压为1200V,容量为630kVA,MYP-3×25+1×15mm2电缆长度为100m
MYP-3×25+1×15mm2电缆的电阻、电抗: 查附录三表5得,R1=0.864Ω X1=0.088Ω
Rz1=0.864×0.1=0.0864Ω
Xz1=0.088×0.1=0.0088Ω ∑R=0.2219+0.0864=0.3083Ω ∑X=0.20419+0.0088=0.21299Ω
Id4=Ue/2(∑R2+∑X2)0.5=1200/2(0.30832+0.212992)0.5=1601A (6)工作面供电系统图中风机电机前两相短路电流Id5的计算
已知变压器二次电压为690V,容量为315kVA,MY-3×50+1×16电缆长度为400m,MY-3×16+1×4电缆长度为10m。
MY-3×50+1×16电缆的电阻、电抗: MY-3×16+1×4电缆的电阻、电抗: 查附录三表5得,R1=0.448Ω X1=0.081Ω R2=1.37Ω X2=0.09Ω
Rz1=0.448×0.4=0.1792Ω
Xz1=0.081×0.4=0.0324Ω
Rz2=1.37×0.01=0.0137Ω
Xz2=0.09×0.01=0.0009Ω
∑R=0.015896+0.1792+0.0137=0.208796Ω ∑X=0.0968+0.0324+0.0009=0.1301Ω Id6=Ue/2((∑R2+∑X2))0.5=690/2(0.2087962+0.13012)0.5=1402A (四)低压形开关整定
(1)工作面供电系统图中B1 KBSGZY-630kVA移变低馈开关Iz1的整定值 皮带机×1 55kW Ie1=35.75A 涨紧绞车×1 7.5kW Ie2=5.2A 刮板机×1 55kW Ie3=35.75A 照明综保×1 4kVA Ie4=2.41A 简易皮带×1 30kW Ie5=18.6A
综掘机×1 300kW Ie6=118.6+56+8.2=182.8A Iqe=711.6A P=300+55+55+30+7.5+18.5+4=470kW 1、过流保护动作电流: Ie1=Pe/(30.5Uecosф)
=0.7×300/(1.732×1.2×0.8)+0.4×170/(1.732×1.2×0.6) =180.8A
过流保护动作电流实际整定值:180A 2、短路保护动作电流:
最大电机总功率Pe=300kW;最大电机起动电流Iqe=711.6A 速断保护电流整定计算: Iz1≥Iqe+Kx∑Ie
=711.6+0.7×(56+8.2)+0.4×(35.75+5.2+2.4+18.6)=781.32A 短路保护电流实际整定值:1080A(即6Ie1) 校验灵敏度系数; Id2/Iz1=1990/1080=1.8>1.5 满足灵敏度要求。
(2)工作面B1 KBSGZY-630-6/1.2电源高压防爆开关过电流Iz2的整定值: 1、过流保护动作电流:
Ie2=0.7×Pe /(30.5Uecosф)+ 0.4×Pe /(30.5Uecosф) =0.7×300/(1.732×6×0.8)+0.4×170/(1.732×6×0.6) =36.1A
过流保护动作电流实际整定值:35A 2、短路保护动作电流:
最大电机总功率Pe=300kW;最大电机起动电流Iqe=144.3A 速断保护电流整定计算: Iz2≥Iqe+Kx∑Ie
=144.3+0.7×(300-200)/( 1.732×6×0.8)+ 0.4×115/(1.732×6×0.6)
=152.9A
短路保护电流实际整定值:210A(即6Ie2)
(3)工作面供电系统图中d1开关BKD16-400 Iz3的整定值 皮带机×1 55kW Ie1=35.75A 涨紧绞车×1 7.5kW Ie2=5.2A 刮板机×1 55kW Ie3=35.75A 照明综保×1 4kVA Ie4=2.41A 简易皮带×1 30kW Ie5=18.6A
综掘机×1 300kW Ie6=118.6+56+8.2=182.8A P=300+55+55+30+7.5+18.5+4=470kW 1、额定保护动作电流: Ie3=Ie+0.7∑Ie+0.4∑Ie
=118.6+0.7×(56+8.2)+0.4×170 =180.8A
额定保护动作电流实际整定值:180A 2、短路保护动作电流:
最大电机总功率Pe=200kW;最大电机起动电流Iqe=711.6A 速断保护电流整定计算: Iz3≥Iqe+Kx∑Ie
=711.6+0.7×(56+8.2)+0.4×115
Iqe=711.6A