12.10 视频监控系统 .......................................................................................................................................... 34 12.11 火灾报警系统 .......................................................................................................................................... 34 12.12 安全防范工程 .......................................................................................................................................... 34 12.13 控制室 ...................................................................................................................................................... 34 附录A 防护屏障的防护范围 ................................................................................................................................ 35 本规范用词说明 ....................................................................................................................................................... 37 本规范引用标准名录 ............................................................................................................................................... 38
2
Table of contents
1 General rule............................................................................1 2 Term .......... ... ....................................................................2 3 Hazard classes of building and explosive quantity.......................................4 3.1 Hazard classes of building………………………………………………………………………………4 3.2 Explosive quantity…………………………………………………………………………………………7 4 Engineering planning and exterior minimum separation distances..........................8 4.1 Engineering planning………………………………………………………………………………………8 4.2 Exterior minimum separation distances in hazard particles production area…………………8 4.3 Exterior minimum separation distances in general magazine area of hazardous particles…8 4.4 Exterior minimum separation distances in destruction ground and testing area………………13 5 General plan layout and interior minimum separation distances...........................14 5.1 General plan layout………………………………………………………………………………………14 5.2 Interior minimum separation distances in hazard production area………………………………14 5.3 Interior minimum separation distances in general magazine area of hazardous particles……16 5.4 Protecting barrier………………………………………………………………………………………18 6 Process and layout.......................................................................19 7 Storage and transportation of hazardous particles........................................20 7.1 Storage of hazardous particles…………………………………………………………………………20 7.2 Transportation of hazardous particles………………………………………………………………20 8 Building structure.......................................................................21 8.1 General………………………………………………………………………………………………………21 8.2 Structure selection and construction of hazard production area………………………………21 8.3 Blast resistant chamber and blast resistant yard……………………………………………………22 8.4 Emergency evacuation of hazardous buildings in production area…………………………………22 8.5 Structure of buildings in hazard production area……………………………………………………23 8.6 Structure of buildings in general magazine area of hazardous particles………………………23 8.7 Corridor and tunnel………………………………………………………………………………………24 9 Fire fighting............................................................................25 10 Treatment of waste water.................................................................26 11 Heating, ventilation and air conditioning................................................27 11.1 Heating……………………………………………………………………………………………………27 11.2 Ventilation and air conditioning……………………………………………………………………27 12 Electrical installation in hazardous location..........................................28 12.1 Classification of hazardous location………………………………………………………………28 12.2 Electrical equipment……………………………………………………………………………………30 12.3 Indoor electrical wiring………………………………………………………………………………31 12.4 Lighting system…………………………………………………………………………………………32
3
12.5 10kv & under power distribution substations and power distribution room in production building.32 12.6 Outdoor electrical wiring……………………………………………………………………………32 12.7 Lightning protection and earthing……………………………………………………………………33 12.8 Electrostatic prevention………………………………………………………………………………33 12.9 Communication……………………………………………………………………………………………34 12.10 Television monitoring system…………………………………………………………………………34 12.11 Fire alarm system………………………………………………………………………………………34 12.12 Security and protection system………………………………………………………………………34 12.13 Control chamber…………………………………………………………………………………………34 Appendix A protection area of protecting barrier.........................................35 Explanations of the words used in this code...............................................37 Appendix explanations of this code........................................................38
4
1 总 则
1.0.1 为贯彻《中华人民共和国安全生产法》,坚持“安全第一、预防为主、综合治理”的方针,规范烟花爆竹工程建设,预防和减少生产安全事故,保障人民群众生命和财产安全,促进烟花爆竹行业安全、持续、健康发展,特制定本规范。
1.0.2 本规范适用于烟花爆竹生产企业和经营(批发)企业仓库的新建、改建和扩建工程设计;本规范不适用于经营(零售)烟花爆竹的储存,以及军用烟火的制造、运输和储存。
1.0.3 本规范涉及外部安全,在烟花爆竹生产企业和经营(批发)企业仓库周边规划建设居民点、企业、城镇、重要设施时,必须遵守本规范的规定。
1.0.4 烟花爆竹生产企业和经营(批发)企业仓库的工程设计,除应执行本规范规定外,本规范未规定的部分应符合国家现行有关规范、标准的规定。
1
2 术 语
2.0.1 烟花爆竹生产企业 fireworks and firecracker Industry
指生产烟花、爆竹及生产用于烟花、爆竹产品的黑火药、烟火药、引火线、电点火头等的企业。 2.0.2 危险品 hazardous product
指本规范范围内的烟火药、黑火药、引火线、氧化剂等,以及用以上物品制成的烟花、爆竹在制品、半成品、成品。
2.0.3 在制品 in-process product 指正在各生产阶段加工的产品。 2.0.4 半成品 semi-finished product
指在某些生产阶段上已完工,尚需进一步加工的产品。
2.0.5 危险品生产厂房 production building of hazardous product 生产、制造、加工危险品的建筑物。 2.0.6 中转库 transit store
在生产过程中,在厂区内用于暂存药物、半成品、成品、引火线及有药部件的建(构)筑物。 2.0.7 总仓库 general store
指集中储存成品、化工原材料、药物(黑火药、烟火药、亮珠、药柱、药块)、效果内筒、引火线的仓库。
2.0.8 临时存药洞 temporary explosive storage cave
指在危险性建筑物附近自然山体内镶嵌的临时存放药物的洞室。 2.0.9 危险性建筑物 hazardous building
生产或储存危险品的建(构)筑物,包括危险品生产厂房、储存库房、晒场、临时存药洞等。 2.0.10 计算药量 explosive quantity
能形成同时爆炸或燃烧的危险品最大药量。 2.0.11 摩擦类药剂 friction ignited powder
含氯酸钾、硫化锑、雷酸银等药剂,经摩擦能产生引燃(爆)作用的药剂。 2.0.12 笛音剂 whistling powder
含高氯酸钾、苯甲酸氢钾、苯二甲酸氢钾等药剂,能产生哨音效果的药剂。 2.0.13 爆炸音剂 powder with detonation sonud
含高氯酸盐、硝酸盐、硫磺、硫化锑、铝粉等药剂,能产生爆炸音响效果的药剂。 2.0.14 外部最小允许距离 external minimum allowable distance
指危险性建筑物与外部各类目标之间,在规定的破坏标准下所允许的最小距离。它是按建筑物的危险等级和计算药量确定的。
2.0.15 内部最小允许距离 interior minimum allowable distance
指危险品厂房、库房与相邻建筑物之间,在规定的破坏标准下所允许的最小距离。它是按建筑物的危险等级和计算药量确定的。
2.0.16 防护屏障 protecting barrier
有天然屏障和人工屏障,其形式、强度均能按规定方式限制爆炸冲击波、碎片、火焰对附近建筑物及设施的影响。
2.0.17 人均使用面积 useable floor area per capita
厂房内有效使用面积按作业人员平均,每个作业人员所占有的面积。 2.0.18 轻型泄压屋盖 light relief roof
泄压部分(不包括檩条、梁、屋架)由轻质材料构成,当建筑物内部发生事故时,具有泄压效能,使建筑物主体结构尽可能不受到破坏的屋盖。
轻型泄压部分的单位面积重量不应大于0.8kN/m2。 2.0.19 轻质易碎屋盖 light fragile roof
由轻质易碎材料构成,当建筑物内部发生事故时,不仅具有泄压效能,且破碎成小块,减轻对外部影响的屋盖。
轻质易碎部分的单位面积重量不大于1.5kN/m2。
2